Download Print this page

Siemens LMV5 Quick Start Manual page 146

Hide thumbs Also See for LMV5:

Advertisement

Error
Diag.
Device
Display
code
code
Any #
LMV5/
Fault Running
Act./ VSD
Time
01..3F
Fault Running
01
Time Air Actuator
Fault Running
Act. /
04
Time Aux
1D
LMV5
Actuator
Fault Running
08
Time Aux
Actuator
VSD /
Fault Running
10
LMV5..
Time VSD
Fault Running
Act. /
20
Time Aux
LMV5
Actuator
Act. /
Any #
LMV5.. /
VSD
01..3F
01
Act.
Special Pos not
1E
02
reached
04
08
10
VSD Sys.
20
Act.
LMV5 QSG Rev 4
Meaning for the LMV5x system
Fault with Actuator (VSD) Positioning, Actuator (VSD) Run Time
Running time fault of actuators or VSD.
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format)
Running time fault of air actuator
Running time fault of auxiliary actuator 1
Running time fault of auxiliary actuator 2
Running time fault of VSD
Running time fault of auxiliary actuator 3
Basic unit has detected that 1 / several actuators (incl. VSD
module) has / have not reached the special position pertaining
to the Phase
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format)
Positioning fault of air actuator
Positioning fault of fuel actuator
Positioning fault of auxiliary actuator 1
Positioning fault of auxiliary actuator 2
VSD has not reached the speed
Positioning fault of auxiliary actuator 3
Sec 5 Pg 20
Corrective action
1) Check parameters (TimeNoFlame) and
(OperatRampMod). These should be set to values
greater than the ramping timeof the attached actuators
or VSD.
2) Check connected actuators to determine if their
torque rating is being exceed (stuck damper or valve
etc...)
3) Check the two 12V fuses located under black covers
on the right side of the LMV5
4) Check the CANBus power supply (blue or black
transformer) Pin 1 and Pin 4 should have 12VAC to
reference ground which is pin 2. Voltage betwen Pin 1
and Pin 4 should be 24VAC.
1) Check connected actuators to determine if their
torque rating is being exceed (stuck damper or valve
etc...)
2) Check the two 12V fuses located under black covers
on the right side of the LMV5
3) Check the CANBus power supply (blue or black
transformer) Pin 1 and Pin 4 should have 12VAC to
reference ground which is pin 2. Voltage betwen Pin 1
and Pin 4 should be 24VAC.
4) If a VSD is being used, check for filters, damping and
or delays on the input signal to the VSD. The VSD
should respond to the input signal in a linear fashion.
See Error Code 15
www.scccombustion.com