Section 10-1 Component Specifications
LMV5 Base Unit (120volt)
Category
Mains Voltage (max)
Mains Voltage (min)
Power
Mains Frequency (min)
Requirements
Mains Frequency (max)
Typ. Power Consumption
Fuse FU1 Rating 5 x 20 mm 250 volt Slow-Blow
Fuses
Fuse FU2 Rating 5 x 20 mm 250 volt Slow-Blow
Fuse FU3 Rating 5 x 20 mm 250 volt Slow-Blow
Total Current to all outputs, thru safety loop (X3-04.1 / X3-
04.2) and burner flange (X3-03.2 / X3-03.1) at any given
time
Fan motor contactor (X3-01.1)
Alarm (X3-01.2)
Ignition transformer (X4-02.3)
Pilot Valve (X9-01.2)
Gas Valve 1 (X9-01.4)
Gas Valve 2 (X9-01.3)
Maximum
Gas Valve SV (X9-01.1)
ratings for
Oil Valve1 (X8-02.1)
Mains Voltage
Outputs
Oil Valve1 (X8-03.1)
Oil Valve 2 (X7-01.3)
Oil Valve 3 (X7-02.3)
Oil Valve SV (X6.03.3)
Oil pump contactor (X6-02.3)
Oil Indicator (X8-01.2)
Gas Indicator (X8-01.1)
Start Signal, (X4-03.3)
Power signals for switches, flame detector
12VAC1 for CANbus power, 12 VAC (X50.2, X51.2)
Maximum
12VAC2 for can bus power, 12 VAC (X50.3, X51.3)
ratings for
Low Voltage
Power supply for pressure / temp transducers, 20 VDC
Outputs
Power supply for QRI flame detector 14 / 21 VDC
Weight
Chassis weight
Ambient Temperature (min)
Environmental
Ambient Temperature (max)
Maximum humidity
Enclosure
IP rating (first number objects, second water)
Mounting
All Orientations
Notes :
Ingress of water and ice are not permitted.
Use wire suitable for maximum terminal ratings
For CANBus wiring, use specified cable only.
LMV5 QSG Rev 4
Description
Sec 10 Pg 1
Units
Value
132
Volts AC
102
Volts AC
47
Hz
63.6
Hz
30
Watts
6.3
Amps
4
Amps
4
Amps
5
Amps
1
Amps
1
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1.6
Amps
1
Amps
1
Amps
0.5
Amps
0.5
Amps
4
Amps
4
Amps
25
mA
100
mA
3
lb
o
-4
F
o
140
F
95
% R.H.
IP20
N/A
N/A
N/A
ww.scccombustion.com