Menu Path
Parameter
ASN
Params & Display>
ProductionDate
AZL>
SerialNumber
ParamSet Code
ProductID
ParamSet Vers
Params & Display>
SW Version
AZL
1 AirActuator
2 GasActuat(Oil)
3 OilActuator
Params & Display>
Actuators>
Addressing
4 AuxActuator1
5 AuxActuator2
6 AuxActuator3
6 AuxActuator3
DeleteCurves
1 AirActuator
2 GasActuat(Oil)
Params & Display>
Actuators>
3 OilActuator
DirectionRot
4 AuxActuator1
5 AuxActuator2
6 AuxActuator3
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
Information concerning the AZL.
U
Software Version on the AZL
Enables addressing of the actuators. Select one of the actuators and press enter.
The AZL will then serve as a guide through the rest of the procedure.
This procedure involves pressing a red button (hold about 1 sec.) on the selected actuator. The actuators
can be wired and addressed in any order. The green LED will be on when the actuator is powered and not
addressed, and it will blink then pause after it has been addressed.
1 blink = Air,
2 blinks = gas or gas(oil),
S
3 blinks = oil,
4 blinks = aux1,
5 blinks = aux2,
6 blinks = aux3
Holding the red button on the actuator down for approx 10 seconds will clear the addressing on that actuator
Holding the red button on the actuator down for approx 10 seconds will clear the addressing on that actuator.
This deletes the ratio control (fuel / air) curves. Curves must be deleted if the direction of rotation on any
actuator is changed.
Sets the direction of rotation for each actuator, regardless of which fuel is selected.
If you are looking at the actuator with the shaft pointed directly at you,
Standard Rotation would be counterclockwise,
O
Reversed Rotation would be clockwise.
These descriptions are opposite if viewed from the cover end of the actuator. (shaft pointing away from you)
Range = Standard, Reversed Def = Standard
Sec 4 Pg 51
Descriptions / Notes
All
0
12
All
www.scccombustion.com