Siemens LMV5 Quick Start Manual page 106

Hide thumbs Also See for LMV5:

Advertisement

Menu Path
Parameter
Params & Display>
SW Version
Load Controller
PasswordTime
Params & Display>
Sum/WinterTime
AZL>
Times
Time EU/US
Language
Params & Display>
AZL
DateFormat
Params & Display>
PhysicalUnits
AZL
Params & Display>
Address
AZL>
Ebus
SendCycleBU
Address
Baudrate
Parity
Params & Display>
Timeout
AZL>
ModBus
Lokal / Remote
Remote Mode
W3
Params & Display>
Display Contrast
AZL
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
U Software version of the load controller
O Sets the length of time for the password to time out. Range =10 to 400 min. Def = 120 min.
Automatic: Daylight savings automatically, Manual: Disables daylight savings time feature.
Daylight savings time schedule. US setting START: 1st Sun in Apr END: last Sun in Oct.
Select the language you want the AZL to display. Default is English.
Date format has 2 Choices: MM-DD-YY (US) or DD.MM.YY (European) Default is US.
Either °C / bar or °F / psi can be chosen. Def = °F / psi.
Sets the LMV address for Ebus (job specific...) Range = 1 to 8 Def = 1
Sets the cycle time for the LMV to send data to the BAS (job specific...)
Range = 10 to 60 sec Def = 30 sec
Sets the LMV address for Modbus (job specific...) Range = 1 to 247 Def = 1
U
Sets the baud rate of the ModBus port, which is an RJ45 jack located on the underside of the AZL. NOTE:
To use ModBus, it must be activated at: Operation > Optgmodeselect. Def = 9600
This sets the parity of the ModBus port. Range = Parity , No Parity Def = no parity.
If no communication occurs for this period, the AZL considers the ModBus to be unavailable. If the AZL
considers the Modbus to be unavailable, then it will make setpoint W1 the current setpoint. Other ModBus
values will remain what they were previous to the unavailability, and or be overwritten by input though the
AZL. Range = 0 to 7200s Def / Typ = 30 s
This enables or disables the use of a ModBus conveyed setpoint, setpoint W3. Lokal: (local) W3 will not be
observed. Remote: there is no timeout condition and the remote operating mode is automatic then setpoint
W3 will be observed.
View the ModBus "Remote Mode" status: Automatic, On, Off
W3 is the ModBus conveyed setpoint. Range = 0 to 3632 degrees F or 1500 PSIG
< >
Change with
keys store with Enter key, cancel with the Esc key.
Sec 4 Pg 50
Descriptions / Notes