Actuator Options
SQM45.291A9
27 in / lb of torque
SQM45.295A9
27 in / lb of torque
SQM48.497A9
177 in / lb of torque
SQM48.697A9
310 in / lb of torque
Note:
All actuators offer:
The same footprint
Identical actuator mounting holes
Have a 90 degree operating range
Positioning accuracy of 0.1 degree
Rotate either clockwise or counterclockwise
Inquire about
SCC actuator brackets and zero lash flexible
application
couplings are available and highly recommended to
guide
ensure trouble-free actuator operation.
Couplings will accommodate up to 3
parallel misalignment with no appreciable side load.
Note:
SCC never recommends soild couplings.
Flame Detector Options and Accessories
(The LMV5 does not require a flame signal amplifier)
QRI2A2.B180B
Sensor is self checking, forward viewing
(IR) detector (continuous use)
AGG2.110
3/4" threaded holder for QRI2A2. B180B forward viewing
scanner, with a thermal barrier, and protective lens
QRI2B2.B180B
Sensor is self checking, side viewing
(IR) detector (continuous use)
AGG2.120
Conduit connection adapter for QRI 3/4" NPSM thread
QRA75.A17
Self checking side viewing Ultra Violet (UV)
flame detector (designed for continuous use)
AGM23U
12 foot cable used with the QRA75
AGG16.U
QRA75 Right Angle Adapter, allows the side viewing
UV scanner to be used on forward viewing applications
Female thread is 3/4"-14 NPT
THERMAL-1X75
Optional thermal barrier for use with the AGG16.U
Male Thread 1"-11.5 NPSM, Female thread 3/4"-14 NPT
the LMV5 and utilize integral flame signal amplifiers.
LMV5 QSG Rev 4
10-120 seconds
10 mm round keyed shaft
10-120 seconds
10 mm "D" shaped shaft
30-120 seconds
14 mm round keyed shaft
60-120 seconds
14 mm round keyed shaft
o
angular and 0.06"
Sec 1
Pg 3
www.scccombustion.com