Setting Parameters Via The Device Menu - Siemens SENTRON PAC2200 Product Manual

7km measuring device
Hide thumbs Also See for SENTRON PAC2200:
Table of Contents

Advertisement

Commissioning
6.3 Parameterizing the device
"Hardware write-protection" parameter
No write access is possible, even if password information is used. In order to gain write
access, the hardware write protection must be deactivated.
ON: Hardware write protection is activated.
OFF: Hardware write protection is deactivated
Activation or deactivation of the password protection must be confirmed on the device.
Request message "PRESS SW" appears on the display for 15 minutes. By pressing the SW
key on the device during this phase, the protection function is activated or deactivated.
"Access protection IP filter" parameter
The IP filter is a configurable access protection. If activated, Modbus TCP write commands
are only accepted if the remote station is located in the same subnet.
Note
It is recommended to activate the hardware write protection on the device.
6.3.2

Setting parameters via the device menu

The PAC2200 device can be parameterized via the "Settings" menu option.
Note chapter Menu navigation (Page 51)
The menu guidance language can be set in the "Settings" menu by selecting the "Language"
option.
This enables you to select either English or German. English is the default setting.
"Language" parameter
The menu guidance language can be set in the "Settings" menu by selecting the "Language"
option.
This enables you to select either English or German. English is the default setting.
"Basic settings" parameter
Not available for 65 A devices.
62
PAC2200
Manual, 05/2018, L1V30415167B-02