Processor Problems - Lenovo ThinkSystem SR850P Maintenance Manual

Hide thumbs Also See for ThinkSystem SR850P:
Table of Contents

Advertisement

c. (Trained technician only) Reseat the operator information panel cable, and then repeat steps 2a and
2b.
• (Trained technician only) If the server starts, replace the operator information panel.
• If the server does not start, go to step 3.
3. Make sure that both power supplies installed in the server are of the same type. Mixing different power
supplies in the server will cause a system error (the system-error LED on the front panel turns on).
4. Make sure that:
• The power cords are correctly connected to the server and to a working electrical outlet.
• The type of memory that is installed is correct.
• The DIMMs are fully seated.
• The LEDs on the power supply do not indicate a problem.
• The processors are installed in the correct sequence.
5. Reseat the following components:
a. Operator information panel connector
b. Power supplies
6. Replace the following components. restarting the server each time:
a. Operator information panel connector
b. Power supplies
7. If you just installed an optional device, remove it, and restart the server. If the server now starts, you
might have installed more devices than the power supply supports.
8. See
"Power supply LEDs" on page
Server does not power off
Complete the following steps until the problem is resolved:
1. Determine whether you are using an Advanced Configuration and Power Interface (ACPI) or a non-ACPI
operating system. If you are using a non-ACPI operating system, complete the following steps:
a. Press
Ctrl+Alt+Delete
b. Turn off the server by pressing the power-control button and holding it down for 5 seconds.
c. Restart the server.
d. If the server fails POST and the power-control button does not work, disconnect the power cord for
20 seconds; then, reconnect the power cord and restart the server.
2. If the problem remains or if you are using an ACPI-aware operating system, suspect the system board.
Unexpected shutdown with LED not lit
Complete the following steps until the problem is resolved:
1. Check the XCC event log, and resolve related errors if found any.
2. Reseat power supply.
3. If the error recurs, replace power supply.

Processor problems

Use this information to solve problems related to a monitor or video.
"The server goes directly to the POST event viewer when it is turned on." on page 159
ThinkSystem SR850P Maintenance Manual
158
140.
.

Advertisement

Table of Contents
loading

This manual is also suitable for:

7d2f7d2g7d2h

Table of Contents