Trouble Call Limit (Dialer Runaway Prevention) - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

3.6.9.2.4.2 Backup Reporting
The DACT can be programmed to transmit reports to primary and/or secondary central station
phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the
following screen:
Press 1 to have all reports transmitted to the central station secondary phone number as a
backup only if the primary phone line fails, 2 to transmit all reports to both the primary and
secondary phone numbers all of the time or 3 to send reports to the first available phone
number.

3.6.9.2.5 Trouble Call Limit (Dialer Runaway Prevention)

The Call Limit option limits the number of DACT trouble calls to the Central Station, to a
programmed amount between 0 and 99, for each unique trouble within a 24 hour period.
Separate limit counters keep track of each unique type of trouble. Note that the number of
phone line (communication) faults called to the Central Station are not limited by this feature.
No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose
call limit has been reached. Local DACT annunciation will still track the particular trouble and
restoral.
To set the Trouble Call Limit, press 3 while viewing Central Station Screen #1. The following
screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
Note: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the
Central Station an unlimited number of times. This is the factory default setting.
MS-9050UD PN 52413:C 01/23/08
BACKUP REPORTING
1=BACKUP ONLY
2=BOTH
3=FIRST AVAILABLE
Backup Reporting Screen
TROUBLE CALL LIMIT
00-99 RANGE
*
Backup Reporting Screen
Programming
121