The programmer can select the notification appliance output by pressing the number
corresponding to the desired output. The coding selections are:
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second
off
Two Stage 3 Minutes or 5 Minutes - Refer to "Two Stage Operation" on page 99. for a
description of this feature
Selection of one of the above options will cause the control panel to store the information in
memory and return the display to NAC Screen #2, which will display the new coding choice.
3.6.5.5.5.1 Two Stage Operation
Two Stage operation consists of the following:
If Two Stage operation is programmed as the Coding option, the following sequence of events
will occur during an alarm.
1. The on-board NACs which are programmed to General Alarm Zone 0 will activate with a
2. If the activated alarm point is directly mapped to a zone which is programmed to an on-
3. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not been
4. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation
5. If another alarm point is activated and the countdown timer is counting, the alarm point
6. If another alarm point is activated and the countdown timer has stopped counting due to
7. Any control modules assigned to special Zone 19 will be activated either by direct
8. Control modules that are programmed to the same zone as the activated input device will
MS-9050UD PN 52413:C 01/23/08
1st stage output - 20 ppm (pulse-per-minute) coding
2nd stage output - Temporal coding as described above
1st stage output upon activation of any alarm point
board NAC, that NAC will go directly to 2nd stage coding output. All other NACs not
directly mapped to the activated alarm point's zone but assigned to Zone 0 will activate
with a 1st stage output
pressed, all NACs presently in 1st stage activation will go to 2nd stage activation
will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already
in 2nd stage activation
will have no effect on the NACs unless the alarm point's zones are directly mapped to
one of the NACs, in which case it will follow the procedure outlined in step 2
the Acknowledge switch being pressed, the countdown timer will restart and the NACs
will respond as outlined in step 2. NACs already in 2nd stage activation will not be
affected
mapping of an input device programmed to Zone 19 or if an NAC enters 2nd stage
operation
not be delayed for activation