Operating Instructions
Addressable Smoke Detectors, Monitor Modules and Control Modules
For addressable devices connected to the SLC loop, the following is a typical message that could
appear on the LCD display for a device trouble:
The information displayed in the above example provides the following information:
First line in display:
Second line in display:
Third line in display: INVREP indicates an invalid reply from the addressable device. Other
possible troubles include:
Fourth line in display:
150
TROUBL SMOKE (PHOTO)
<ADJ> <NOUN>
10:00A 090805 1D001
The type of event; in this example TROUBL indicating a device trouble
Device type identifier; in this example, SMOKE (PHOTO) indicates a Photoelectric
smoke detector. Other device type identifiers which can be displayed include SMOKE
(ION) for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module
and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc. Refer to
"Edit Detector" on page 58, "Edit Module Screen for Monitor Module" on page 68 and
"Edit Module Screen for Control Modules" on page 77 for information on additional
device types.
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
SHORT - indicating a shorted circuit on an addressable device
OPEN - indicating an open circuit on an addressable device
DIRTY1 - maintenance alert indicating that a detector is near but below the allowed
alarm limit and is in need of maintenance before the performance is compromised
DIRTY2 - maintenance alert indicating that a detector needs immediate maintenance
since it has been within 80% of its alarm threshold for 24 hours
INVREP - maintenance alert indicating a hardware problem in the detector
TEST F - indicating a detector has failed the automatic test operation which
functionally checks its sensing chamber and electronics
INV ID - indicating that an incorrect device code (Type ID) has been programmed for
an installed device (for example, Photo has been programmed but an Ion detector has
been installed)
SW TBL - indicating a module has failed the testing of its Class A switching relay
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 09 for September, 08 for the 8th
day of the month and 04 for the year 2004
Device Address; 1D001 in this example 1 represents SLC Loop, D represents a detector
and 001 represents device address 001
INVREP
MS-9050UD PN 52413:C 01/23/08