2.7 Digital Communicator

Two independent telephone lines can be connected to the control panel. Telephone line control/
command is made possible via double line seizure as well as usage of an RJ31X style interconnec-
tion. Note that it is critical that the panel's digital communicator be located as the first device on
the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded per require-
ments of UL 864 9th Edition.
Network
RJ31X
Service
Jack
Provider's
Facilities
Telephone
Line
Network
Demarcation
Point
The control panel's digital communicator is built into the main circuit board. Connection and wir-
ing of two phone lines is required as shown below.
MS-9050UD PN 52413:C 01/23/08
Customer Premises Equipment and Wiring
MS-9050UD
Telephone
Answering
System
Figure 2.8 DACT Installation
Figure 2.9 Wiring Phone Jacks
Unused
RJ-11 Jack
RJ-11 Jack
Fax Machine
Telephone
Installation
Computer
Telephone
Unused
47