Programming
• NFPA 2010 Dual Path: Supervision Interval: 24 Hours
• NFPA 2010 Sole Path: Supervision Interval: 5 min
• NFPA 2013 Dual Path: Supervision Interval: 6 Hours
• NFPA 2013 Sole Path: Supervision Interval: 1 Hour
NOTE: These supervision settings apply to both the Cellular settings and the Ethernet settings.
Cellular
XXX COMM PATH
1=POTS
2=ETHERNET
3=CELLULAR
Comm Path Screen #1
Enable
To enable the Ethernet connection, press 1 while viewing the Ethernet Options Screen #1 to change the display to Enabled Yes. Each
press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Central Station Account
CELLULAR OPTIONS
1=ENABLED
YES
2=CS ACCOUNT
Cellular Options Screen #1
Enter the City ID, Central Station ID, and Account Code all provided by the monitoring station.
Supervision Settings
CELLULAR OPTIONS
1=SUPV. SETTINGS
NFPA 2010 DUAL PATH
Cellular Options Screen #2
used.
• NFPA 2010 Dual Path: Supervision Interval: 24 Hours
• NFPA 2010 Sole Path: Supervision Interval: 5 min
• NFPA 2013 Dual Path: Supervision Interval: 6 Hours
• NFPA 2013 Sole Path: Supervision Interval: 1 Hour
NOTE: These supervision settings apply to both the Cellular settings and the Ethernet settings.

Trouble Report Limit (Dialer Runaway Prevention)

COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
3=TBL REPORT LIMIT
Communicator Screen #2
To set the Trouble Report Limit, press 3 while viewing Communicator Screen #1. The following screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Report Limit to this value. Refer to the table on page 49 for permissible set-
tings.
NOTE: Entering a value of 00 will disable the Trouble Report Limit allowing the Communicator to call the Central Station an unlimited
number of times.
86
To configure the communication method to contact central station as a GSM/Cellular connection, select 3
for Cellular from the Comm Path Screen. The following screens will display. Note that a CELL-MOD or
CELL-CAB-N must be installed in the system for use of this feature.
CELLULAR OPTIONS
1=ENABLED
2=CS ACCOUNT
Cellular Options Screen #1
Press 2 on Cellular Options Screen #1 to display the following:
CS ACCOUNT
1=CITY ID
2=CS ID
3=ACCT CODE
Central Station Account Screen
Pressing 1 while viewing Ethernet Options Screen #2 will cause the display to toggle between the 4 super-
vision setting options. Toggle to select NFPA 2010 Sole Path, NFPA 2010 Dual Path, NFPA 2013 Sole
Path, or NFPA 2013 Dual Path. Refer to the table on page 49 for permissible settings.
The Supervision Interval is the time from the check-in at AlarmNet to the FACP. Select Dual Path when
Ethernet and Cellular communications will be used. Select Sole Path when only Ethernet or Cellular is
The Report Limit option limits the number of Communicator trouble calls to the Central Station, to a pro-
grammed amount between 00 and 99, for each unique trouble within a 24 hour period. Separate limit count-
ers keep track of each unique type of trouble. Note that the number of phone line (communication) faults
0
called to the Central Station are not limited by this feature. No subsequent restoral message is sent to the
Central Station(s) for a particular trouble whose call limit has been reached. Local communicator annuncia-
tion will still track the particular trouble and restoral.
TROUBLE CALL LIMIT

Trouble Report Limit Screen
CELLULAR OPTIONS
NO
1=SUPV. SETTINGS
NFPA 2010 DUAL PATH
Cellular Options Screen #2
0000
0000
000000
00-99 RANGE
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Master Programming Level