SECTION 3
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be lim-
ited to specific values or not used at all as indicated below:
Program feature
Permitted in
or option
UL 864? (Y/N)
Trouble Call Limit
Remote Download

3.1 Programming Data Entry

Programming can be accomplished using the MS-9050UD keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J6 on the
control panel main circuit board.
The information presented in this section refers to programming the MS-9050UD via the onboard
keypad. If an optional computer keyboard is connected to the MS-9050UD main circuit board, the
following table describes the keyboard keys which correspond to the onboard keypad keys.
MS-9050UD PN 52413:C 01/23/08

Programming

AND OTHER INVOLVED PARTIES
Refer to "Trouble Call Limit (Dialer Runaway Preven-
tion)" on page 121.
Trouble Call Limit = 0 (factory default): unlimited
N
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Refer to "Remote Download" on page 176.
Y
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Keypad Keys
1st Event
CLR
ESC
RECALL
*
#
A - Z
0 - 9
(on QZ key)
/
ENTER
ACK/STEP
SILENCE
DRILL
RESET
Possible settings
Computer Keyboard Keys
Home
Delete
Esc
Insert
*
#
A - Z
0 - 9
Space bar
/
Enter
F1
F2
F3
F4
Programming
Settings permitted in
UL 864
Trouble Call Limit = 0
for unlimited Central
Station
trouble calls
Remote Download
Proprietary Yes for
Proprietary
Installations Only