Powering Ann-Bus Devices From Auxiliary Power Supply; Ann-Bus Device Addressing - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

1.9.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply

Figure 1.3 illustrates the powering of ANN-BUS devices from an auxiliary power supply such
as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANN-
BUS power requirements.
FCPS-24FS6/8

1.9.2 ANN-BUS Device Addressing

Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 106).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
Note: Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
MS-9050UD PN 52413:C 01/23/08
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
-24 VDC
+24 VDC
Figure 1.3 Powering ANN-BUS Devices from FCPS-24FS6/8
Address
Switch 5
not valid
OFF
OFF
01
OFF
OFF
02
OFF
OFF
03
OFF
OFF
04
OFF
OFF
05
OFF
OFF
06
OFF
OFF
07
OFF
OFF
08
OFF
ON
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS
MS-9050UD
Switch 4
Switch 3
Switch 2
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
Product Description
ANN-80
Switch 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF