6: Trouble Zone - Honeywell NOTIFIER NFS2-3030 Programming Manual

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

Program
Soft Keys
LOGIC FUNCTION: Press to scroll through the list of possible logic functions.
ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and to
return to the previous screen.
Add Time/Date
This screen appears when the ADD TIME/DATE soft key is pressed at the Logic Zone
Programming Menu screen
Soft Keys
ENTER TIME: _ _:_ _:_ _ Press this soft key to toggle between the time/date formats. Choose one
based on the type of time-based function used.
Time-based
function
DEL, SDEL, TIM ENTER TIME:_ _:_ _:_ _
TIM
TIM
3.4.6 Trouble Zone
Trouble Zone Programming
Trouble zones provide a means of using a system trouble input to effect an output. For instance, an
annunciator trouble can be used to activate an output device.
The trouble zone format is ZTxxx, where xxx is a number from one through one hundred. When a
trouble zone format is entered at the Point Select screen, the same programming screens and
choices appear as for logic zones, except the zone format is a trouble zone format. (Refer to
paragraphs "Logic Zone Programming" on page 51 and the paragraphs following "Add
Time/Date").
Refer to Appendix E, "CBE: Zones and Equations" for information on how to create a trouble
equation, and how they operate.
54
L O G I C Z O N E P R O G R A M M I N G M E N U
L O G I C Z O N E Z L x x x x
A U T O M A T I C O F F
D E L
O V E R W R I T E
E N T E R T I M E : 2 2 : 3 0 : 0 0
Figure 3.41 Add Time/Date to Logic Zone Screen
Screen Field
ENTER DATE:_ _-_ _-_ _ (MM-DD-YY)
ENTER DAY: MO
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Time/date format
HH:MM:SS, entered as military time (22:30:00 = 10:30 P.M.)
(Use the TOGGLE DAY soft key that appears to scroll through
and choose a day of the week.
Point Program