The Zones Installed screen will show the system zones (default and user programmed) and their
associated types. Note that an up and/or down arrow will appear in the upper right corner of the
display, indicating that additional screens of zone information exists. Press the up or down
arrow keys to view zones Z00 through Z19.
Zone types can be changed by pressing the keypad number key corresponding to the zone in
each Zones Installed Screen. Available zone types will be displayed in the resultant screens.
For example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The
following screens will be displayed:
ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program
Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will
return to the Zones Installed Screen showing zone Z02 and the Pull Station program type.
Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a
Waterflow silenceable zone type to the selected zone. Any signaling devices programmed to the
same zone can be silenced by pressing the Alarm Silence key or by using the auto-silence
feature.
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page 89.
Note: Zone Types are only relevant for Central Station reporting. Changing a zone type will
only change how it is reported to the Central Station.
MS-9050UD PN 52413:C 01/23/08
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
Zone Type Program Screen #4
ZONE TYPE PROG
1=NONE
Zone Type Program Screen #5
Programming
87