Table 7.3 contains columns for calculating current draws. For each column, calculate the current
and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 7.4 on page 182.
Calculation Column 1
Primary, Non-Fire Alarm Current
Device Type
(amps)
Qty
Main Circuit Board
1
4XTMF
[
]
4-wire Detector Heads
[
]
Power Supervision
[
]
3
Relays
CP350 & CP355
[
]
SD350 & SD355
[
]
SD350T & SD355T
[
]
AD350 & AD355
[
]
H350 & H355
[
]
H350R & H355R
[
]
H355HT
[
]
D350P
[
]
D350RP
[
]
4
[
]
B501BH & B501BHT
B224RB Relay Base
[
]
B224BI Isolator Base
[
]
MMF-300
[
]
MMF-300-10
[
]
MDF-300
[
]
MMF-301
[
]
MMF-302
[
]
MMF-302-6
[
]
BG-12LX
[
]
CMF-300
[
]
CMF-300-6
[
]
CRF-300
[
]
CRF-300-6
[
]
I300
[
]
ANN-80
[
]
ANN-I/O
[
]
ANN-RLY
[
]
ANN-(R)LED
[
]
ANN-S/PG
[
]
5
NAC #1
NAC #2
6
Sum each column
for totals
Primary Non-Alarm =
Table Footnote
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
2. Refer to the Device Compatibility Document for standby current.
3. Must use compatible listed Power Supervision Relay.
4. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
5. Current limitation of Terminal TB1 circuits is 2.5 amps total max.
6. Total current draw listed above cannot exceed 2.7 amps.
MS-9050UD PN 52413:C 01/23/08
Table 7.3 System Current Draw Calculations
Calculation Column 2
Primary, Fire Alarm Current
(amps)
X[current draw]=
Total
Qty
X[0.120]=
0.120
1
X[0.005]=
[
2
[
X[
]
=
X[0.025]=
[
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.00030]=
X[0.001]=
X[0.00050]=
X[0.00045]=
X[0.00040]=
X[0.00350]=
X[0.00075]=
X[0.000375]=
X[0.00027]=
X[0.00200]=
X[0.00023]=
X[0.00039]=
X[0.00225]=
X[0.00027]=
X[0.00145]=
X[0.00040]=
X[0.0370]=
[
X[0.0350]=
[
X[0.0150]=
[
X[0.0280]=
[
X[0.0450]=
[
[
[
Primary Alarm =
X [current draw] =
Total
X[0.200]=
0.200
1
]
X[0.011]
=
]
X[
]=
]
X[0.025]=
maximum alarm draw
0.400
for all devices
]
X[0.0400]=
]
X[0.2000]=
]
X[0.0750]=
]
X[0.0680]=
]
X[0.0450]=
]
X[
]=
]
X[
]=
Power Supply Calculations
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
Qty
X[current draw]=
Total
1
X[0.120]=
0.120
[
]
X[0.005]=
[
]
X[
]=
[
]
X[0.025]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.001]=
[
]
X[0.00050]=
[
]
X[0.00045]=
[
]
X[0.00040]=
[
]
X[0.00350]=
[
]
X[0.00075]=
[
]
X[0.000375]=
[
]
X[0.00027]=
[
]
X[0.00200]=
[
]
X[0.00023]=
[
]
X[0.00039]=
[
]
X[0.00225]=
[
]
X[0.00027]=
[
]
X[0.00145]=
[
]
X[0.00040]=
[
]
X[0.0150]=
[
]
X[0.0350]=
[
]
X[0.0150]=
[
]
X[0.0280]=
[
]
X[0.0450]=
Secondary Non-Alarm =
181