Programming
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
110
ANN-LED Options Screen
Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-LED
option is selected, will display the following screen:
ZONES
ALARM, TRBL, SUPV
1=POINT/ZONE
2=ALARM/ATS
3=RANGE
The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed
to annunciate Alarms, Troubles and Supervisories for Zones 00 through 09. The programming
can be changed using ANN-LED Address Screen 2.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module
to annunciate either Point (addressable device address) information or Zone information. Each
press of the 1 key will toggle the display between Point and Zone.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module
to annunciate only Alarms or Alarms, Troubles and Supervisories (ATS). Each press of the 2
key will toggle the display between Alarms and ATS.
Pressing 3 while viewing ANN-LED Address Screen #2 will select the Point or Zone range to
be annunciated (refer to the tables in "ANN-RLED Zone Option - Alarm Only" on page 111
and "ANN-RLED Point Option - Alarm Only" on page 113). Pressing the 3 key will display an
additional screen where the range can be selected.
If Zone has been selected, and Alarms Only are to be annunciated, the 3 key will have no
effect since all zones can be displayed on only one ANN-LED module.
If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the
new screen will give the options of annunciating Zone 0 - 9 or 10 - 19. Two ANN-LED
modules are required to annunciate all zones in this configuration.
If Points has been selected, and Alarms Only are to be annunciated, the new screen will give
the options of annunciating Points 1 - 30 and 31 - 50. Two ANN-LED modules are required
to annunciate all points in this configuration.
If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the
new screens will give the options of annunciating Points 1 - 10, 11 - 20, 21 - 30, 31 - 40 or 41
- 50. Five ANN-LED modules are required to annunciate all points in this configuration.
ANN-LED ADDR #
00-09
ANN-LED Address Screen #1
ANN-LED ADDR #
ZN00-09
ANN-LED Address Screen #2
ZONE
ATS