CS1W-PTS01-V1 Isolated-type Thermocouple Input Unit

2-1
CS1W-PTS01-V1 Isolated-type Thermocouple Input Unit
Overview
System Configuration
Features
30
The CS1W-PTS01-V1 Isolated-type Thermocouple Input Unit provides four
direct thermocouple inputs, and sends the data to the CPU Unit each cycle.
All inputs are isolated.
4 thermocouple inputs
(K, J, B, E, N, R, S, T, or mV)
• Up to four thermocouples can be directly connected to each Unit (with
four separate settings for temperature sensors and input ranges).
• Isolation between inputs prevents sneak circuits from occurring between
thermocouple inputs.
• This Unit is suitable for a wide range of temperature specifications. K, J,
B, E, N, R, S, or T can be selected.
• Temperature sensor values are transmitted to the CPU Unit in four digits
hexadecimal.
• Variable input range setting.
• Four values for each process value alarm input.
• ON-delay timer for process value alarm.
• Mean value processing.
• Rate-of-change calculation.
• Two values for each rate-of-change alarm input.
• Zero/span adjustment capability during operation.
• Disconnection detection.
• Maximum or minimum process value can be specified for when a discon-
nection is detected.
CS1W-PTS01-V1