Specifications And Installation; Specifications - Omron CJ Series Operation Manual

Machine automation controller analog i/o units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

1-4

Specifications and Installation

1-4-1

Specifications

The specifications shown in the following table apply to all the Analog I/O Units.
For specifications specific to each Unit, refer to 2-1-6 Specifications for CJ1W-PDC15, 3-1-6 Specifica-
tions for CJ1W-AD04U, and 3-2-6 Specifications for CJ1W-PH41U.
Item
Unit classification
Dimensions
Weight
External terminal
connections
Unit number switch
Self-diagnostic function
Mounting position
Maximum number of
Units
Ambient operating tem-
perature
Ambient operating
humidity
Current consumption
Name
Isolated-type Direct Cur-
rent Input Unit
Isolated-type Universal
Input Units
CJ-series Analog I/O Units Operation Manual for NJ-series CPU Unit(W498)
NJ-series CJ Special I/O Unit
31 × 90 × 65 mm (W × H × D)
150 g max.
18-point removable terminal block (M3 screws, Tightening torque: 0.5 N·m)
00 to 95
Results of self-diagnosis shown on indicators.
NJ-series CPU Rack or Expansion Rack
40 Units (10 Units × 4 Racks)
Confirm that the total current consumption of all the Units (including the CPU Unit)
mounted to a single CPU Rack or Expansion Rack does not exceed the maximum
power supplied by the Power Supply Unit.
0 to 55°C
10% to 90% (with no condensation)
Model
Current consumption (power)
5 V
CJ1W-PDC15
0.18 A (0.9 W)
CJ1W-AD04U
0.32 A (1.6 W)
CJ1W-PH41U
0.30 A (1.5 W)
1 Overview and Features
Specification
24-V external
0.09 A
Not used.
Not used.
1
1-19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-pdc15Cj1w-ph41uCj1w-ad04u

Table of Contents