Process Value Scaling To Industrial Units - Omron CJ Series Operation Manual

Machine automation controller analog i/o units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

1 Overview and Features
1-2-3

Process Value Scaling to Industrial Units

This function takes the value scaled to industrial units with respect to the input signal's zero point and
span point, and outputs it to the CPU Unit as the process value. Because of this, no user program is
required at the CPU Unit for scaling.
It also possible to set the process value scaling zero/span point in reverse to create an inverse relation-
ship.
Applicable Units
4
Input signal
Industrial unit
0
CJ1W-PDC15, PH41U
With the CJ1W-PDC15/-PH41U, the input range for thermocouple inputs, and platinum-resistance
thermometer inputs, or the user-set range for DC inputs can be set directly, and scaling can be set
for the range in industrial units. This eliminates the need for processing scaling in the user program.
It also possible to set the process value scaling zero/span points in reverse to create an inverse rela-
tionship.
With the CJ1W-PH41U, potentiometer input scaling is also possible.
K thermocouple
Minimum input signal value
Minimum scaling value
1-6
Isolated-type Direct Current Input Unit
Isolated-type Universal Input Units
20 mA
800 Pa
Measured input range
−200°C
0°C
400°C
Operating
temperature range
0
Scaling range
CJ-series Analog I/O Units Operation Manual for NJ-series CPU Unit(W498)
CJ1W-PDC15
CJ1W-AD04U (voltage/current input)
CJ1W-PH41U
1300°C
Maximum input signal value
10000
Maximum scaling value