Regulations And Standards; General Specifications - Omron GI-SMD/SID Quick Start Manual

Safety i/o terminal
Table of Contents

Advertisement

Specifications

Regulations and Standards

GI-S-series safety I/O terminals
Certification body
• EN ISO 13849-1
• IEC 61508 parts 1-7
TÜV Rheinland
• IEC/EN 62061
• IEC/EN 61131-2
• NRAG (UL 61010-1, UL 61010-2-201 and UL 121201)
UL
• NRAG7 (CSA C22.2 No. 61010-1, CSA C22.2 No. 61010-2-201 and CSA C22.2 No. 213)
• The FSoE protocol was certified for applications in which OMRON FSoE devices are connected to each other.For compatibility with FSoE
devices other than OMRON FSoE devices, the customer must validate FSoE communications.
By using GI-S-series safety I/O terminals, you can build a safety control system that meets the followings.
• Requirements for SIL 3 (Safety Integrity Level 3) in IEC 61508, IEC/EN 62061, (Functional Safety of Electrical/Electronic/Programmable
Electronic Safety-related Systems)
• Requirements for PLe (Performance Level e) and for safety category 4 in EN ISO13849-1
Also, GI-S-series safety I/O terminals have been registered for conformity to RCM, EAC, and KC (Korean radio regulation).

General Specifications

Item
Enclosure
Ambient operating temperature
Ambient operating humidity
Atmosphere
Ambient storage temperature
Altitude
Pollution degree
Insulation class
Overvoltage category
Operating
EMC immunity level
environment
Vibration resistance
Shock resistance
Insulation resistance
Dielectric strength
Installation method
Degree of protection
Standards
Mounted in a panel (open type)
0 to 55°C
10% to 95% (with no condensation or icing)
Must be free from corrosive gases
−25 to 70°C (with no condensation or icing)
2,000 m max.
2
CLASS III (SELV)
II
Zone B: IEC 61131-2
Conforms to IEC 60068-2-6
5 to 8.4 Hz with amplitude of 3.5 mm
8.4 to 150 Hz, acceleration of 9.8 m/s
100 min. in each X, Y, and Z directions (10 sweeps of 10 min. each = 100 min. total)
Conforms to IEC 60068-2-27
147 m/s
2
3 times in each X, Y, and Z directions
20 MΩ between isolated circuits (at 100 VDC)
500 VAC between isolated circuits for 1 minute at a leakage current of 10 mA max.
DIN Track mounting (IEC 60715 TH35-7.5/TH35-15)
IP20