Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 95

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

ALARM
OR
ALERT
NUMBER
T300
Space Temperature Below Limit
T301
Space Temperature Above Limit
T302
Supply Temperature Below Limit
T303
Supply Temperature Above Limit
T304
Return Temperature Below Limit
T305
Return Temperature Above Limit
T308
Return Air Relative Humidity Below Limit
T309
Return Air Relative Humidity Above Limit
T310
Supply Duct Static Pressure Below Limit
T311
Supply Duct Static Pressure Above Limit
T312
Building Static Pressure Below Limit
T313
Building Static Pressure Above Limit
T314
IAQ Above Limit
A404
Fire Shut Down Emergency Mode (fire-smoke)
A405
Evacuation Emergency Mode
A406
Pressurization Emergency Mode
A407
Smoke Purge Emergency Mode
T408
Dirty Air Filter
A409
Supply Fan Status Failure
T409
Supply Fan Status Failure
T414
Loss of Communication with the Belimo Actuator
T414
Belimo Actuator Direction Error
T414
Belimo Actuator Failure
T414
Belimo Actuator Jammed
T414
Belimo Actuator Range Error
R-W1 Jumper Must Be Installed to Run Heat in Service
T420
Test
T421
Thermostat Y2 Input ON without Y1 ON
T422
Thermostat W2 Input ON without W1 ON
T423
Thermostat Y and W Inputs ON
T424
Thermostat G Input OFF on a Call for Cooling
T500
Current Sensor Board Failure - A1
T501
Current Sensor Board Failure - A2
T502
Current Sensor Board Failure - B1
T503
Current Sensor Board Failure - B2
A700
Supply Air Temperature Sensor Failure
T701
Staged Gas Thermistor 1 Failure
T702
Staged Gas Thermistor 2 Failure
T703
Staged Gas Thermistor 3 Failure
A704
Staged Gas Leaving Air Temp Sum Total Failure
T705
Limit Switch Thermistor Failure
LEGEND
Axxx — Alarm
CEM — Controls Expansion module
IAQ
— Indoor Air Quality
OAT — Outdoor Air Temperature
For 48/50A2,A3,A4,A5 units:
• Compressor internal overload protector is open. Internal
overload protectors are used in the Copeland compressors in
all units except size 60 ton units with voltages of 208/230-v,
380-v, and 575-v.
• Compressor external overload protector (Kriwan module)
has activated. The Copeland compressors in size 60 ton
units with voltages of 208/230-v, 380-v, and 575-v use
external overload protector modules that are mounted in the
compressor wiring junction box. Temperature sensors
embedded in the compressor motor windings are the inputs
to the module. The module is powered with 120 vac from
the units main control box. The module output is a normally
closed contact that is wired in series with the compressor
contactor coil. In a compressor motor overload condition,
the contact opens de-energizing the compressor contactor.
• Circuit breaker trip. The compressors are protected from
short circuit by a breaker in the control box. On the 020-050
Table 114 — Alert and Alarm Codes (cont)
DESCRIPTION
Pxxx — Pre-Alert
Txxx — Alert
TXV
— Thermostatic Expansion Valve
VFD — Variable Frequency Drive
ACTION TAKEN BY CONTROL
Stop cooling, but continue
to heat
Stop heating, but continue
to cool
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Alert
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Unit Shutdown
Run power exhaust
Run supply fan
Run supply and exhaust fans
Continue to run unit
Stop unit
Continue to run unit
Close economizer
Close economizer
Attempt to close economizer
Close economizer
Close economizer
No heat
Assume Y2 is Y1
Assume W2 is W1
Alert
Turn fan on
Stop compressor A1
Stop compressor A2
Stop compressor B1
Stop compressor B2
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
size units there is one breaker per two compressors and on
the 060 size units there is one breaker per compressor.
• Wiring Error. A wiring error might not allow the compres-
sor to start.
To check out alerts 051, 052, 055 and 056:
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most likely
the problem is one of the following: HPS open, open
internal protection, circuit breaker trip, incorrect safety
wiring, or incorrect compressor wiring.
2. If the compressor does start verify it is rotating in the
correct direction.
IMPORTANT: Prolonged operation in the wrong direction
can damage the compressor. Correct rotation can be veri-
fied by a gage set and looking for a differential pressure
rise on start-up.
95
RESET
PROBABLE CAUSE
METHOD
Automatic
Outdoor dampers stuck, no load
Automatic
High load, dampers open
Dampers open, check configuration
Automatic
setpoint
Dampers open, check configuration
Automatic
setpoint
Dampers open, check configuration
Automatic
setpoint
Dampers open, check configuration
Automatic
setpoint
Automatic
Configuration error, or sensor error
Dampers open, check configuration
Automatic
setpoint
Automatic
VFD problem, broken fan belt
Automatic
VFD problem, broken fan belt
Automatic
Exhaust issues, check setpoint
Automatic
Exhaust issues, check setpoint
Automatic
Damper or IAQ control issues
Smoke detector switch or external
Automatic
switch
Automatic
Special fire mode control
Automatic
Special fire mode control
Automatic
Special fire mode control
Automatic
Dirty filter, switch setting
Automatic
Fan drive failure
Automatic
Fan drive failure, or sensor failure
Calibrate economizer, economizer
Automatic
failure, wiring
Automatic
Motor direction switch wrong, wiring
Automatic
Motor failure
Automatic
Obstruction in damper
Automatic
Calibrate economizer
Automatic
Add red wire jumpers
Automatic
Thermostat wiring error
Automatic
Thermostat wiring error
Automatic
Thermostat issues
Automatic
Thermostat or wiring issues
Automatic
Faulty board or wiring
Automatic
Faulty board or wiring
Automatic
Faulty board or wiring
Automatic
Faulty board or wiring
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty switch or wiring