Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 122

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

POINT
POINT DESCRIPTION
NAME
INPUTS
SFS
Supply Fan Status switch
DMD_SW1
Demand Limit - SW1
DMD_SW2/
Demand Limit - SW2/
DHD ISCIN
Dehumidification Switch Input
PRES
Pressurization
EVAC
Evacuation
PURG
Purge
IAQIN
Indoor Air Quality Switch
DMDLMTMA
4-20mA Demand Limit
EDTRESMA
4-20mA Evaporator Discharge SP Reset
OAQ
Outside Air CO
SPRESET
SP Reset milliamps
CEM_10K1/
CEM AN1 10k temp J5,1-2/
CEM_4201
CEM AN1 4-20 ma J5,1-2
CEM_10K2/
CEM AN2 10k temp J5,3-4/
CEM_4202
CEM AN2 4-20 ma J5,3-4
CEM_10K3/
CEM AN3 10k temp J5,5-6/
CEM_4203
CEM AN3 4-20 ma J5,5-6
CEM_10K4/
CEM AN4 10k temp J5,7-8/
CEM_4204
CEM AN4 4-20 ma J5,7-8
Table 120 — IGC Board Inputs and Outputs
POINT NAME
POINT DESCRIPTION
INPUTS
RT
24 Volt Power Supply
W
Heat Demand
G
Fan
LS
Limit Switch
RS
Rollout Switch
SS
Hall Effect Sensor
CS
Centrifugal Switch (Not Used)
FS
Flame Sense
OUTPUTS
CM
Induced Draft Motor
IFO
Indoor Fan
R
24 Volt Power Output (Not Used)
SPARK
Sparker
LED
Display LED
SCROLLING MARQUEE — This device is the keypad in-
terface used to access the control information, read sensor
values, and test the unit. The scrolling marquee display is a
4-key, 4-character, 16-segment LED display as well as an
Alarm Status LED. See Fig. 30. The display is easy to operate
using 4 buttons and a group of 11 LEDs that indicate the
following menu structures:
• Run Status
• Service Test
• Temperatures
• Pressures
• Set points
• Inputs
• Outputs
• Configuration
• Timeclock
• Operating Modes
• Alarms
Through the scrolling marquee the user can access all the
inputs and outputs to check on their values and status. Because
the unit is equipped with suction pressure transducers and
discharge saturation temperature sensors it can also display
Table 119 — Controls Expansion Board (CEM) Inputs
Sensor
2
CONNECTOR
PIN NO.
R1,C
2
3
7,8
5,6
1,2,3
9,10
FS
CM
IFO
R
I/O POINT
PLUG AND PIN
NAME
REFERENCE
DI 1
J7, 1-2
DI 2
J7, 3-4
DI 3
J7, 5-6
DI 4
J7, 7-8
DI 5
J7, 9-10
DI 6
J7, 11-12
DI 7
J7, 13-14
AN7
J6, 1-3
AN8
J6, 4-6
AN9
J6, 7-9
AN10
J6, 10-12
AN10
J6, 10-12
AN1
J5, 1-2
AN2
J5, 3-4
AN3
J5, 5-6
AN4
J5, 7-8
AN5
J5, 9-10
AN6
J5, 11-12
pressures typically obtained from gages. The control includes a
full alarm history, which can be accessed from the display. In
addition, through the scrolling marquee the user can access a
built-in test routine that can be used at start-up commission and
to diagnose operational problems with the unit. The scrolling
marquee is located in the main control box and is standard on
all units.
SUPPLY FAN — The size 020 to 050 units are equipped with
two 15 x 11-in. forward-curved fans. The size 051 and 060
units have three 15 x 11-in. fans. They are on a common shaft
and are driven by single belt drive 3-phase motor. The fan is
controlled directly by the ComfortLink™ controls.
VARIABLE FREQUENCY DRIVE (VFD) — On variable
volume units, the supply fan speed is controlled by a 3-phase
VFD. The VFD is located in the fan section behind a remov-
able panel as shown in Fig. 24 and 25. The VFD speed is
controlled directly by the ComfortLink controls through a 4 to
20 mA signal based on a supply duct pressure sensor. The
inverter has a display, which can be used for service diagnos-
tics, but setup of the supply duct pressure set point and control
loop factors is done through the scrolling marquee display. The
VFD is powered during normal operation to prevent condensa-
tion from forming on the boards during the off mode and is
stopped by driving the speed to 0 (by sending a 2 mA signal to
the VFD).
The A Series units use ABB ACH550 VFDs. The interface
wiring for the VFDs is shown in Fig. 31. Terminal designations
are shown in Table 121.
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Fig. 30 — Scrolling Marquee
122
SIGNAL PIN(S)
PORT STATE
2
0 = 24vac, 1= 0vac
4
0 = 24vac, 1= 0vac
6
0 = 24vac, 1= 0vac
8
0 = 24vac, 1= 0vac
10
0 = 24vac, 1= 0vac
12
0 = 24vac, 1= 0vac
14
0 = 24vac, 1= 0vac
2 (1 = loop power)
(0-20mA input)
5 (4 = loop power)
(0-20mA input)
8 (7 = loop power)
(0-20mA input)
11 (10 = loop power)
(0-20mA input)
11 (10 = loop power)
(0-20mA input)
1
(thermistor, ohms)
3
(thermistor, ohms)
5
(thermistor, ohms)
7
(thermistor, ohms)
9
(thermistor, ohms)
11
(thermistor, ohms)
Alarm Status
ESCAPE
ENTER
A30-2239