Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 76

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

REMOTE
SWITCH LOGIC
SWITCH
CONFIGURATION
STATUS
(RMI.L)
OPEN
OPEN
CLOSED
OPEN
CLOSED
CLOSED
Monday In Period (PER.X
able is used to include or remove Monday from the schedule.
Each period is assigned an occupied on and off time. If this
variable is set to YES, then Monday will be included in that peri-
od's occupied time schedule. If this variable is set to NO, then
the period's occupied time schedule will not be used on Monday.
This variable can be set for Periods 1 through 8.
Tuesday In Period (PER.X
is used to include or remove Tuesday from the schedule. Each
period is assigned an occupied on and off time. If this variable
is set to YES, then Tuesday will be included in that period's oc-
cupied time schedule. If this variable is set to NO, then the peri-
od's occupied time schedule will not be used on Tuesday. This
variable can be set for Periods 1 through 8.
Wednesday In Period (PER.X
variable is used to include or remove Wednesday from the
schedule. Each period is assigned an occupied on and off time.
If this variable is set to YES, then Wednesday will be included
in that period's occupied time schedule. If this variable is set to
NO, then the period's occupied time schedule will not be used
on Wednesday. This variable can be set for Periods 1 through 8.
Thursday In Period (PER.X
able is used to include or remove Thursday from the schedule.
Each period is assigned an occupied on and off time. If this
variable is set to YES, then Thursday will be included in that
period's occupied time schedule. If this variable is set to NO,
then the period's occupied time schedule will not be used on
Thursday. This variable can be set for Periods 1 through 8.
Friday In Period (PER.X
used to include or remove Friday from the schedule. Each peri-
od is assigned an occupied on and off time. If this variable is set
to YES, then Friday will be included in that period's occupied
time schedule. If this variable is set to NO, then the period's oc-
cupied time schedule will not be used on Friday. This variable
can be set for Periods 1 through 8.
Saturday In Period (PER.X
able is used to include or remove Saturday from the schedule.
Each period is assigned an occupied on and off time. If this
variable is set to YES, then Saturday will be included in that
period's occupied time schedule. If this variable is set to NO,
then the period's occupied time schedule will not be used on
Saturday. This variable can be set for Periods 1 through 8.
Sunday In Period (PER.X
is used to include or remove Sunday from the schedule. Each
period is assigned an occupied on and off time. If this variable
is set to YES, then Sunday will be included in that period's oc-
cupied time schedule. If this variable is set to NO, then the peri-
od's occupied time schedule will not be used on Sunday. This
variable can be set for Periods 1 through 8.
Holiday In Period (PER.X
is used to include or remove a Holiday from the schedule. Each
period is assigned an occupied on and off time. If this variable is
set to YES, then holidays will be included in that period's occu-
pied time schedule. If this variable is set to NO, then the period's
occupied time schedule will not be used on holidays. This vari-
able can be set for Periods 1 through 8.
Table 92 — Remote Switch Logic Configuration
REMOTE INPUT STATE
(REMT)
OFF
ON
ON
OFF
DAYS
MON) — This vari-
DAYS
TUE) — This variable
DAYS
WED) — This
DAYS
THU) — This vari-
DAYS
FRI) — This variable is
DAYS
SAT) — This vari-
DAYS
SUN) — This variable
DAYS
HOL) — This variable
REMOTE SWITCH CONFIGURATION (RM.CF)
0
No Remote Switch
Occ-Unocc Switch
xxxxx
Unoccupied
xxxxx
Occupied
xxxxx
Occupied
xxxxx
Unoccupied
Occupied From (PER.X
configure the start time of the Occupied period. All days in the
same period set to YES will enter into Occupied mode at this
time.
Occupied To (PER.X
figure the end time of the Occupied period. All days in the
same period set to YES will exit Occupied mode at this time.
Local Holiday Schedules (HOL.L) —
is used to program the local holiday schedules. Up to 30 holi-
days can be configured. When a holiday occurs, the unit will
follow the occupied schedules that have the HOLIDAY IN
PERIOD point set to YES.
Holiday Start Month (HD.01 to HD.30
the start month for the holiday. The numbers 1 to 12 corre-
spond to the months of the year (e.g., January = 1).
Holiday Start Day (HD.01 to HD.30
start day of the month for the holiday. The day can be set from
1 to 31.
Holiday Duration (HD.01 to HD.30
length in days of the holiday. The holiday can last up to 99
days.
Daylight Savings Time (DAY.S) —
ings time function is used in applications where daylight
savings time occurs. The function will automatically correct
the clock on the days configured for daylight savings time.
DAYLIGHT SAVINGS START (DS.ST) — This submenu
configures the start date and time for daylight savings.
Daylight Savings Start Month (DS.ST
the start month for daylight savings time. The numbers 1 to 12
correspond to the months of the year (e.g., January = 1).
Daylight Savings Start Week (DS.ST
the start week of the month for daylight savings. The week can
be set from 1 to 5.
Daylight Savings Start Day (DS.ST
start day of the week for daylight savings. The day can be set
from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Add (DS.ST
is the amount of time that will be added to the time clock for
daylight savings.
DAYLIGHT SAVINGS STOP (DS.SP) — This submenu con-
figures the end date and time for daylight savings.
Daylight Savings Stop Month (DS.SP
the stop month for daylight savings time. The numbers 1 to 12
correspond to the months of the year (e.g., January = 1).
Daylight Savings Stop Week (DS.SP
the stop week of the month for daylight savings. The week can
be set from 1 to 5.
Daylight Savings Stop Day (DS.SP
stop day of the week for daylight savings. The day can be set
from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Subtract (DS.SP
This is the amount of time that will be removed from the time
clock after daylight savings ends.
76
1
2
Start/Stop
Start
No Override
Stop
Stop
Start
No Override
OCC) — This variable is used to
UNC) — This variable is used to con-
This submenu

MON) — This is
DAY) — This is the
LEN) — This is the
The daylight sav-
ST.MN) — This is
ST.WK) — This is
ST.DY) — This is the
MIN.A) — This
SP.MN) — This is
SP.WK) — This is
SP.DY) — This is the
3
Override
Override
Override
MIN.S) —

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Weathermaker 48aj 020-060Weathermaker 50aw 020-060Weathermaker 48ay 020-060Weathermaker 50ay 020-060Weathermaker 50aj 020-060Weathermaker 48a4 020-060 ... Show all

Table of Contents