Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 143

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

ITEM
4-20
4-20 MILLIAMP INPUTS
IAQ.M
IAQ Milliamps
OAQ.M
OAQ Milliamps
SP.R.M
SP Reset milliamps
DML.M
4-20 ma Demand Signal
EDR.M
EDT Reset Milliamps
ORH.M
OARH Milliamps
RRH.M
RARH Milliamps
BP.M
BP Milliamps
BP.M.T
Bldg. Pressure Trim (ma)
SP.M
SP Milliamps
SP.M.T
Static Press. Trim (ma)
*The display text changes depending on the remote switch configuration (Configuration
Switch), then the display text will be "On" or "Off." If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be "Occupied" or
"Unoccupied." If RM.CF is set to 2 (Start/Stop), then the display text will be "Stop" or "Start." If RM.CF is set to 3 (Override Switch), then the display
text will be "No Override" or "Override."
ITEM
FANS
FANS
S.FAN
Supply Fan Relay
S.VFD
Supply Fan VFD Speed
P.E.A
Power Exhaust Relay A
P.E.B
Power Exhaust Relay B
P.E.C
Power Exhaust Relay C
CD.F.A
Condenser Fan Circuit A
CD.F.B
Condenser Fan Circuit B
COOL
COOLING
A1
Compressor A1 Relay
A2
Compressor A2 Relay
MLV
Min. Load Valve (HGBP)
B1
Compressor B1 Relay
B2
Compressor B2 Relay
HEAT
HEATING
HT.1
Heat Relay 1
HT.2
Heat Relay 2
HT.3
Relay 3 W1 Gas Valve 2
HT.4
Relay 4 W2 Gas Valve 2
HT.5
Relay 5 W1 Gas Valve 3
HT.6
Relay 6 W2 Gas Valve 3
H.I.R
Heat Interlock Relay
ECON
ECONOMIZER
ECN.P
Economizer Act.Curr.Pos.
ECN.C
Economizer Act.Cmd.Pos.
E.PWR
Economizer Power Relay
GEN.O
GENERAL OUTPUTS
ALRM
Remote Alarm/Aux Relay
ITEM
UNIT
UNIT CONFIGURATION
Machine Control Type
C.TYP
CV.FN
Fan Mode (0=Auto, 1=Cont)
RM.CF
Remote Switch Config
CEM
CEM Module Installed
TCS.C
Temp.Cmp.Strt.Cool Factr
TCS.H
Temp.Cmp.Strt.Heat Factr
SFS.S
Fan Fail Shuts Down Unit
SFS.M
Fan Stat Monitoring Type
VAV.S
VAV Unocc.Fan Retry Time
SIZE
Unit Size (20-60)
DP.XR
Disch.Press. Transducers
SP.XR
Suct. Pres. Trans. Type
RFG.T
Refrig: 0=R22 1=R410A
CND.T
Cnd HX Typ:0=RTPF 1=MCHX
MAT.S
MAT Calc Config
MAT.R
Reset MAT Table Entries?
MAT.D
MAT Outside Air Default
ALTI
Altitude........in feet:
DLAY
Startup Delay Time
STAT
TSTAT-Both Heat and Cool
AUX.R
Auxiliary Relay Config
SENS
INPUT SENSOR CONFIG
SENS
SPT.S
Space Temp Sensor
SENS
SP.O.S
Space Temp Offset Sensor
SENS
SP.O.R
Space Temp Offset Range
SENS
RRH.S
Return Air RH Sensor
SENS
FLT.S
Filter Stat.Sw.Enabled ?
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS (cont)
EXPANSION
–2.0 - 2.0
–2.0 - 2.0
MODE — OUTPUTS
EXPANSION
ON/OFF
0-100
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0-100
0-100
ON/OFF
ON/OFF
MODE — CONFIGURATION
EXPANSION
1 - 6 (multi-text strings)
0 - 1 (multi-text strings)
0 - 3 (multi-text strings)
Yes/No
0 - 60
0 - 60
Yes/No
0 - 2 (multi-text strings)
0 - 720
20 - 60
Yes/No
0 - 1 (multi-text strings)
0 - 1 (multi-text strings)
0 - 1 (multi-text strings)
0 - 2 (multi-text strings)
Yes/No
0-100
0 - 60000
0 - 900
Yes/No
0 - 3
Enable/Disable
Enable/Disable
1 - 10
Enable/Disable
Enable/Disable
RANGE
UNITS
ma
IAQ_MA
ma
OAQ_MA
ma
SPRST_MA
ma
DMDLMTMA
ma
EDTRESMA
ma
OARH_MA
ma
RARH_MA
ma
BP_MA
BPMATRIM
ma
SP_MA
SPMATRIM
UNIT
RANGE
UNITS
SFAN_RLY
%
SFAN_VFD
PE_A
PE_B
PE_C
CONDFANA
CONDFANB
CMPA1
CMPA2
MLV
CMPB1
CMPB2
HS1
HS2
HS3
HS4
HS5
HS6
HIR
%
ECONOPOS
%
ECONOCMD
ECON_PWR
ALRM
RANGE
UNITS
min
min
min
%
sec
143
CCN POINT
WRITE STATUS
forcible
config
config
RM.CF). If RM.CF is set to 0 (No Remote
CCN POINT
WRITE STATUS
forcible
forcible
forcible
forcible
CCN POINT
DEFAULT
CTRLTYPE
4
27,28,32,35-37,
63,75,96
FAN_MODE
1
27,28,35,36
RMTINCFG
0
31,35,36,74
CEM_BRD
No
35,36
TCSTCOOL
0
35,36
TCSTHEAT
0
36
SFS_SHUT
No
36,60,100
SFS_MON
0
35,36,60,100
SAMPMINS
50
36
UNITSIZE
20
36,38,42,49
DP_TRANS
No
36,97
SPXRTYPE
0
36
REFRIG_T
1
36,38,49
COILTYPE
0
36,38,49
MAT_SEL
1
36,47,48
MATRESET
No
36,47,48
MATOADOS
20
36,37
ALTITUDE
0
36,37
DELAY
0
36,37
TSTATALL
No
36,37
AUXRELAY
0
36,37
36
SPTSENS
Disable
27,28,36,37
SPTOSENS
Disable
36,37,75
SPTO_RNG
5
36,37,75
RARHSENS
Disable
36,37,61,97,99
FLTS_ENA
Disable
36,37,60,100
PAGE NO.