POINT
POINT DESCRIPTION
NAME
INPUTS
GASFAN
YAC Indoor Fan relay (fan request from YAC)
FSD
Fire Shutdown switch input
G
Thermostat 'G' input
W2
Thermostat 'W2' input
W1
Thermostat 'W1' input
Y2
Thermostat 'Y2' input
Y1
Thermostat 'Y1' input
CSB_A1
Compressor A1 current sensor
CSB_A2
Compressor A2 current sensor
CSB_B1
Compressor B1 current sensor
CSB_B2
Compressor B2 current sensor
Circuit A saturated
DP_A/SCTA
condensing pressure/temp
Circuit B saturated
DP_B/SCTB
condensing pressure/temp
Circuit A saturated
SP_A/SSTA
suction pressure/temp
Circuit B saturated
SP_B/SSTB
suction pressure/temp
RAT
Return air temperature
SA_TEMP
Supply air temperature
OAT
Outdoor air temperature
SPT
Space temperature (T55/56)
SPTO
Space temperature offset (T56)
IAQ/IAQMINOV
IAQ analog input
FLTS
Filter Status
OUTPUTS
CMPB2
Compressor B2
CMPB1
Compressor B1
CMPA2
Compressor A2
CMPA1
Compressor A1
CONDFANB
Condenser fan B
CONDFANA
Condenser fan A
HS2
Heat stage 2
HS1
Heat stage 1
HIR
Heat interlock relay
SF
Supply fan
ALRM
Alarm output relay
YAC — Gas Heat Unit
RED LED - STATUS
J1
J2
J3
J4
J5
J6
J7
Table 115 — Main Control Board (MBB) Inputs and Outputs
I/O POINT
NAME
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DIG1
DIG2
DIG3
DIG4
AN1
AN2
AN3
AN4
AN5
AN6
AN7
AN8
AN9
AN10
AN11
RLY 1
RLY 2
RLY 3
RLY 4
RLY 5
RLY 6
RLY7
RLY 8
RLY 9
RLY 10
RLY 11
GREEN LED-
LEN (LOCAL EQUIPMENT NETWORK)
CEPL130346-01 HK 50AA029 CE BO 430346
STATUS
LEN
Fig. 26 — Main Base Board (MBB)
PLUG AND PIN
SIGNAL PIN(S)
REFERENCE
J6, 3-4
J6, 5-6
J7, 1-2
J7, 3-4
J7, 5-6
J7, 7-8
J7, 9-10
J9, 10-12
10=5v, 11=Vin, 12=GND
J9, 7-9
7=5v, 8=Vin, 9=GND
J9, 4-6
4=5v, 5=Vin, 6 =GND
J9, 1-3
1=5v, 2=Vin, 3=GND
21=5v, 22=Vin, 23=GND
J8, 21-23
(thermistor 21-22)
24=5v, 25=Vin, 26=GND
J8, 24-26
(thermistor 24-25)
15=5v, 16=Vin, 17=GND
J8, 15-17
(thermistor 15-16)
18=5v, 19=Vin, 20=GND
J8, 18-20
(thermistor 18-20)
J8, 9-10
J8, 11-12
J8, 13-14
J8, 1-2
J8, 3-4
J8, 5-6
J8, 7-8
J10, 20-21
20 = RLY1A (=RLY2A), 21 = RLY1B
J10, 22-23
22 = RLY2A (=RLY1A), 23 = RLY2B
J10, 24-25
24 = RLY3A (=RLY4A), 25 = RLY3B
J10, 26-27
26 = RLY4A (=RLY3A), 27 = RLY4B
J10, 10-11
10 = RLY5A (=RLY6A), 11 = RLY5B
J10, 12-13
12 = RLY6A (=RLY5A), 13 = RLY6B
J10, 14-16
14 = 15 = RLY7A, 16 = RLY7B
J10, 17-19
17 = 18 = RLY8A, 19 = RLY8B
J10, 4-6
4 = 5 = RLY9A, 6 = RLY9B
J10, 7-9
7 = 8 = RLY10A, 9 = RLY10B
J10, 1-3
1 = 2 = RLY11A, 3 = RLY11B
YELLOW LED -
CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER (SET TO 1)
A48-7811
J8
118
PORT STATE
4
0 = 24vac, 1= 0vac
6
0 = 24vac, 1= 0vac
2
0 = 24vac, 1= 0vac
4
0 = 24vac, 1= 0vac
6
0 = 24vac, 1= 0vac
8
0 = 24vac, 1= 0vac
10
0 = 24vac, 1= 0vac
0 = 5vdc, 1 = 0vdc
0 = 5vdc, 1 = 0vdc
0 = 5vdc, 1 = 0vdc
0 = 5vdc, 1 = 0vdc
(0-5vdc, thermistor, ohms)
(0-5vdc, thermistor, ohms)
(0-5vdc, thermistor, ohms)
(0-5vdc, thermistor, ohms)
9
(thermistor, ohms)
11
(thermistor, ohms)
13
(thermistor, ohms)
1
(thermistor, ohms)
3
(thermistor, ohms)
5
(thermistor, ohms)
7
(thermistor, ohms)
1 = Closes RLY1A/RLY1B
1 = Closes RLY2A/RLY2B
1 = Closes RLY3A/RLY3B
1 = Closes RLY4A/RLY4B
1 = Closes RLY5A/RLY5B
1 = Closes RLY6A/RLY6B
1 = Closes RLY7A/RLY7B
1 = Closes RLY8A/RLY8B
1 = Closes RLY9A/RLY9B
1 = Closes RLY10A/RLY10B
1 = Closes RLY11A/RLY11B