ITEM
BP
BUILDING PRESS. CONFIG
BP.CF
Building Press. Config
BP.RT
Bldg.Pres.PID Run Rate
BP.P
Bldg. Press. Prop. Gain
BP.I
Bldg.Press.Integ.Gain
BP.D
Bldg.Press.Deriv.Gain
BP.SO
BP Setpoint Offset
BP.MN
BP VFD Minimum Speed
BP.MX
BP VFD Maximum Speed
BP.FS
VFD/Act. Fire Speed/Pos.
BP.MT
Power Exhaust Motors
BP.S
Building Pressure Sensor
BP.R
Bldg Press (+/-) Range
BP.SP
Building Pressure Setp.
BP.P1
Power Exhaust On Setp.1
BP.P2
Power Exhaust On Setp.2
B.CFG
BP ALGORITHM CONFIGS
B.CFG
BP.SL
Modulating PE Alg. Slct.
B.CFG
BP.TM
BP PID Evaluation Time
B.CFG
BP.ZG
BP Threshold Adjustment
B.CFG
BP.HP
High BP Level
B.CFG
BP.LP
Low BP Level
D.LV.T
COOL/HEAT SETPT. OFFSETS
L.H.ON
Dmd Level
H.H.ON
Dmd Level(+) Hi Heat On
L.H.OF
Dmd Level(-) Lo Heat Off
L.C.ON
Dmd Level
H.C.ON
Dmd Level(+) Hi Cool On
L.C.OF
Dmd Level(-) Lo Cool Off
C.T.LV
Cool Trend Demand Level
H.T.LV
Heat Trend Demand Level
C.T.TM
Cool Trend Time
H.T.TM
Heat Trend Time
DMD.L
DEMAND LIMIT CONFIG.
DM.L.S
Demand Limit Select
D.L.20
Demand Limit at 20 ma
SH.NM
Loadshed Group Number
SH.DL
Loadshed Demand Delta
SH.TM
Maximum Loadshed Time
D.L.S1
Demand Limit Sw.1 Setpt.
D.L.S2
Demand Limit Sw.2 Setpt.
IAQ
INDOOR AIR QUALITY CFG.
DCV.C
DCV ECONOMIZER SETPOINTS
DCV.C
EC.MN
Economizer Min.Position
DCV.C
IAQ.M
IAQ Demand Vent Min.Pos.
AQ.CF
AIR QUALITY CONFIGS
AQ.CF
IQ.A.C
IAQ Analog Sensor Config
AQ.CF
IQ.A.F
IAQ 4-20 ma Fan Config
AQ.CF
IQ.I.C
IAQ Discrete Input Config
AQ.CF
IQ.I.F
IAQ Disc.In. Fan Config
AQ.CF
OQ.A.C
OAQ 4-20ma Sensor Config
AQ.SP
AIR QUALITY SETPOINTS
AQ.SP
IQ.O.P
IAQ Econ Override Pos.
AQ.SP
DAQ.L
Diff.Air Quality LoLimit
AQ.SP
DAQ.H
Diff.Air Quality HiLimit
AQ.SP
D.F.OF
DAQ PPM Fan Off Setpoint
AQ.SP
D.F.ON
DAQ PPM Fan On Setpoint
AQ.SP
IAQ.R
Diff. AQ Responsiveness
AQ.SP
OAQ.L
OAQ Lockout Value
AQ.SP
OAQ.U
User Determined OAQ
AQ.S.R
AIR QUALITY SENSOR RANGE
AQ.S.R
IQ.R.L
IAQ Low Reference
AQ.S.R
IQ.R.H
IAQ High Reference
AQ.S.R
OQ.R.L
OAQ Low Reference
AQ.S.R
OQ.R.H
OAQ High Reference
IAQ.P
IAQ PRE-OCCUPIED PURGE
IAQ.P
IQ.PG
IAQ Purge
IAQ.P
IQ.P.T
IAQ Purge Duration
IAQ.P
IQ.P.L
IAQ Purge LoTemp Min Pos
IAQ.P
IQ.P.H
IAQ Purge HiTemp Min Pos
IAQ.P
IQ.L.O
IAQ Purge OAT Lockout
DEHU
DEHUMIDIFICATION CONFIG.
D.SEL
Dehumidification Config
D.SEN
Dehumidification Sensor
D.EC.D
Econ disable in DH mode?
D.V.CF
Vent Reheat Setpt Select
D.V.RA
Vent Reheat RAT offset
D.V.HT
Vent Reheat Setpoint
D.C.SP
Dehumidify Cool Setpoint
D.RH.S
Dehumidify RH Setpoint
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
EXPANSION
0-3
5-120
0-5
0-2
0-5
0.0 - 0.5
0-100
0-100
0-100
1-2
Enable/Dsable
0 - 1.00
–0.25 -> 0.25
0 - 100
0 - 100
1-3
0 - 10
0.1 - 10.0
0 - 1.000
0 - 1.000
Lo Heat On
–1 - 2
0.5 - 20.0
0.5 - 2
Lo Cool On
–1 - 2
0.5 - 20.0
0.5 - 2
0.1 - 5
0.1 - 5
30 - 600
30 - 600
0 - 3 (multi-text strings)
0 - 100
0 - 99
0 - 60
0 - 120
0 - 100
0 - 100
0 - 100
0 - 100
0 - 4 (multi-text strings)
0 - 2 (multi-text strings)
0 - 2 (multi-text strings)
0 - 2 (multi-text strings)
0 - 2 (multi-text strings)
0 - 100
0 - 1000
100 - 2000
0 - 2000
0 - 2000
–5 - 5
0 - 2000
0 - 5000
0 - 5000
0 - 5000
0 - 5000
0 - 5000
Yes/No
5-60
0-100
0-100
35-70
0-2 (multi-text strings)
1-2 (multi-text strings)
Yes/No
0-1 (multi-text strings)
0-8
55-95
40-55
10-90
RANGE
UNITS
sec
"H2O
%
%
%
"H2O
"H2O
%
%
min
"H2O
"H2O
"H2O
^F
^F
^F
^F
^F
^F
^F
^F
sec
sec
%
%
min
%
%
%
%
%
min
%
%
dF
^F
dF
dF
%
145
CCN POINT DEFAULT
PAGE NO.
BLDG_CFG
0
29,64,65
BPIDRATE
10
64,65
BLDGP_PG
0.5
64,65
BLDGP_IG
0.5
64,65
BLDGP_DG
0.3
64,65
BPSO
0.05
64,65
BLDGPMIN
10
64,65
BLDGPMAX 100
64,65
BLDGPFSO
100
64,65
PWRM
1
64,65
BPSENS
Dsable
64,65
BP_RANGE
0.25
64,65
BPSP
0.05
29,64,65
PES1
35
29,64,65
PES2
75
29,64,65
64,65
BPSELECT
1
64,65
BPPERIOD
1
64,65
BPZ_GAIN
1
64,65
BPHPLVL
0.05
64,65
BPLPLVL
0.04
64-66
DMDLHON
1.5
27,28,52
DMDHHON
0.5
27,28,52
DMDLHOFF 1
27,28,52
DMDLCON
1.5
27,28,52
DMDHCON
0.5
27,28,52
DMDLCOFF 1
27,28,52
CTRENDLV
0.1
52
HTRENDLV
0.1
52
CTRENDTM 120
52
HTRENDTM 120
52
DMD_CTRL
0
31,35,48,49,98
DMT20MA
100
31,49
SHED_NUM 0
49
SHED_DEL
0
49
SHED_TIM
60
49
DLSWSP1
80
31,49
DLSWSP2
50
31,49
ECONOMIN 5
29,31,32,67-70
IAQMINP
0
29,31,67-70
IAQANCFG
0
32,67,69,70
IAQANFAN
0
32,68-70
IAQINCFG
0
31,35,67-70
IAQINFAN
0
32,68-70
OAQANCFG 0
35,68-70
IAQOVPOS
100
32,67,69,70,98
DAQ_LOW
100
68-70
DAQ_HIGH
700
32,68-70
DAQFNOFF
200
32,68-70
DAQFNON
400
32,68-70
IAQREACT
0
69,70
OAQLOCK
0
69,70
OAQ_USER 400
32,69,70
IAQREFL
0
32,69,70
IAQREFH
2000
32,69,70
OAQREFL
0
69,70
OAQREFH
2000
69,70
IAQPURGE
No
69,70
IAQPTIME
15
69,70
IAQPLTMP
10
69,70
IAQPHTMP
35
69,70
IAQPNTLO
50
69,70
DHSELECT
0
69-71
DHSENSOR 1
69,70
DHECDISA
Yes
69,70
DHVHTCFG 0
70,71
DHVRAOFF
0
70,71
DHVHT_SP
70
70,71
DHCOOLSP 45
70,71
DHRELHSP
55
70,71