Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 125

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

TERMINAL
TERMINAL
BOARD
NO.
TB-1 - POWER CONNECTION OR DISCONNECT (in Main Control Box)
11
TB1
12
13
TB-2 - GROUND (in Main Control Box)
TB2
1
TB-3 - CCN COMMUNICATIONS (HY84HA096) (in Main Control Box)
1
2
3
4
TB3
5
6
7
8
TB-4 - THEROMSTAT CONNECTIONS (HY84HA090) (in Main Control Box)
1
2
3
4
TB4
5
6
7
8
TB-5 - FIELD CONNECTIONS (HY84HA101) (in Main Control Box)
1
2
3
4
5
6
7
8
TB5
9
10
11
12
13
14
15
16
TB-6 - FIELD CONNECTIONS (HY84HA101) (in Main Control Box)
1
2
3
4
5
6
7
8
TB6
9
10
11
12
13
14
15
16
TB-7 - ELECTRIC HEAT POWER BLOCK (in Electric Heat section)
1
TB7
2
3
Table 122 — Field Connection Terminal Strips
DESCRIPTION
L1 power supply
L2 power supply
L3 power supply
Neutral Power
LEN +
LEN C
LEN –
24 VAC
CCN +
CCN c
CCN –
Grd
Thermostat R
Thermostat Y1
Thermostat Y2
Thermostat W1
Thermostat W2
Thermostat G
Thermostat C
Thermostat X
VAV Heater Interlock Relay, Ground
VAV Heater Interlock Relay, 24 VAC
T56 Sensor
T56/T58 Ground
T58 Setpoint
Indoor Air IAQ Remote Sensor/Remote Pot/Remote 4-20 mA
Indoor Air IAQ Remote Sensor/Remote Pot/Remote 4-20 mA
Smoke Detector Remote Alarm
Smoke Detector Remote Alarm
Fire Shutdown
Fire Shutdown
Fire Control Common
Fire Pressurization
Fire Evacuation
Fire Smoke Purge
Not Used
Remote Occupied/Economizer Enable 24 VAC
Remote Economizer Contact
Remote Occupied Contact
Demand Limit Contacts Common
Demand Limit Switch 1
Demand Limit Switch 2/Dehumidify Switch Input
Demand Limit 4-20 mA
Demand Limit 4-20 mA
Remote Supply Air Setpoint 4-20 mA
Remote Supply Air Setpoint 4-20 mA
Outdoor Air IAQ 4-20 mA
Outdoor Air IAQ 4-20 mA
IAQ Remote Switch
IAQ Remote Switch
Supply Fan Status Switch
Supply Fan Status Switch
L1 Power Supply
L2 Power Supply
L3 Power Supply
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
24 VAC
5 VDC, logic
5 VDC, logic
5 VDC, logic
ground
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
24VAC
external 24 VDC relay
4-20 mA, ext. powered w/res or 0-5 VDC
4-20 mA, ext. powered w/res or 0-5 VDC
external contacts
external contacts
24 VAC external
external contact
external contact
external contact
external contact
external contact
external 24 VAC contact
external 24 VAC contact
external 24 VAC contact
external 24 VAC contact
external 24 VAC contact
external 24 VAC contact
externally powered 4-20 mA
externally powered 4-20 mA
externally powered 4-20 mA
externally powered 4-20 mA
external contact
external contact
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
125
TYPE
5 VDC, logic
5 VDC, logic
5 VDC, logic
external 24 VDC relay
5VDC
5VDC
5VDC
externally powered 4-20 mA
externally powered 4-20 mA