Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 47

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

ITEM
COOL
COOLING INFORMATION
C.CAP
Current Running Capacity
CUR.S
Current Cool Stage
REQ.S
Requested Cool Stage
MAX.S
Maximum Cool Stages
DEM.L
Active Demand Limit
SUMZ
COOL CAP. STAGE CONTROL
SMZ
Capacity Load Factor
ADD.R
Next Stage EDT Decrease
SUB.R
Next Stage EDT Increase
R.PCT
Rise Per Percent Capacity
Y.MIN
Cap Deadband Subtracting
Y.PLU
Cap Deadband Adding
Z.MIN
Cap Threshold Subtracting
Z.PLU
Cap Threshold Adding
H.TMP
High Temp Cap Override
L.TMP
Low Temp Cap Override
PULL
Pull Down Cap Override
SLOW
Slow Change Cap Override
Slow Change Cap Override (SLOW) — With a rooftop unit,
the design rise at 100% total unit capacity is generally around
30 F. For a unit with 4 stages, each stage represents about
7.5F of change to EDT. If stages could reliably be cycled at
very fast rates, the set point could be maintained very precisely.
Since it is not desirable to cycle compressors more than 6 cy-
cles per hour, slow change override takes care of keeping the
PID under control when "relatively" close to set point.
SumZ Operation — The SumZ algorithm is an adaptive PID
style of control. The PID is programmed within the control and
the relative speed of staging can only be influenced by the user
through the adjustment of the Z.GN configuration. The capaci-
ty control algorithm uses a modified PID algorithm, with a self
adjusting gain which compensates for varying conditions, in-
cluding changing flow rates across the evaporator coil.
Previous implementations of SumZ made static assump-
tions about the actual size of the next capacity jump up or
down. This control uses a "rise per percent capacity" technique
in the calculation of SumZ, instead of the previous "rise per
stage" method. For each jump, up or down in capacity, the
control will know beforehand the exact capacity change
brought on. Better overall staging control can be realized with
this technique.
SUM Calculation — The PID calculation of the "SUM" is
evaluated once every 80 seconds.
SUM = Error + "SUM last time through" + (3 * Error Rate)
Where:
SUM = the PID calculation, Error = EDT – Cooling Control
Point, Error Rate = Error – "Error last time through"
NOTE: "Error" is limited to between –50 and +50 and "Error
rate" is limited to between –20 and +20.
This "SUM" will be compared against the "Z" calculations
in determining whether cooling stages should be added or
subtracted.
Z Calculation — For the "Z" calculation, the control attempts
to determine the entering and the leaving-air temperature of the
evaporator coil and based upon the difference between the two
during mechanical cooling, and then determines whether to
add or subtract a stage of cooling. This is the adaptive element.
The entering-air temperature is referred to as MAT
(mixed-air temperature) and the leaving-air temperature of the
evaporator coil is referred to as EDT (evaporator discharge
temperature). They are found at the local display under the
Temperatures
CTRL sub-menu.
The main elements to be calculated and used in the calcula-
tion of SumZ are:
1) the rise per percent capacity (R.PCT)
Table 62 — Run Status Cool Display
EXPANSION
RANGE
UNITS
%
CAPTOTAL
COOL_STG
CL_STAGE
CLMAXSTG
%
DEM_LIM
-100 – +100
SMZ
^F
ADDRISE
^F
SUBRISE
RISE_PCT
Y_MINUS
Y_PLUS
Z_MINUS
Z_PLUS
HI_TEMP
LOW_TEMP
PULLDOWN
SLO_CHNG
2) the amount of expected rise for the next cooling stage
addition
3) the amount of expected rise for the next cooling stage
subtraction
The calculation of "Z" requires two variables, Z.PLU used
when adding a stage and Z.MIN used when subtracting a stage.
They are calculated with the following formulas:
Z.PLU = Z.GN * (10 + (4*(–ADD.R))) * 0.6
Z.MIN = Z.GN * (–10 + (4*(–SUB.R))) * 0.6
Where:
Z.GN = configuration used to modify the threshold levels used
for staging (Configuration
ADD.R = R.PCT * (C.CAP – capacity after adding a cooling
stage)
SUB.R = R.PCT * (C.CAP – capacity after subtracting a cool-
ing stage)
Both of these terms, Z.PLU and Z.MIN, represent a thresh-
old both positive and negative upon which the "SUM"
calculation must build up to in order to cause the compressor to
stage up or down.
Comparing SUM and Z — The "SUM" calculation is com-
pared against Z.PLU and Z.MIN.
• If "SUM" rises above Z.PLU, a cooling stage is added.
• If "SUM" falls below Z.MIN, a cooling stage is subtracted.
There is a variable called SMZ which is described in the
reference section and which can simplify the task of watching
the demand build up or down over time. It is calculated as
follows:
If SUM is positive: SMZ = 100*(SUM/Z.PLU)
If SUM is negative: SMZ = –100*(SUM/Z.MIN)
Mixed Air Temperature Calculation (MAT) — The mixed-
air temperature is calculated and is a function of the economiz-
er position. Additionally there are some calculations in the con-
trol which can zero in over time on the relationship of return
and outside air as a function of economizer position. There are
two configurations which relate to the calculation of "MAT."
These configurations can be located at the local display under
Configuration
UNIT.
ITEM
EXPANSION
UNIT
UNIT CONFIGURATION
MAT.S
MAT Calc Config
MAT.R
Reset MAT Table
Entries?
47
CCN POINT
WRITE STATUS
forcible
COOL
Z.GN)
CCN
RANGE
POINT
0 - 2
MAT_SEL
Yes/No
MATRESET
DEFAULTS
1
No