Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

BACNET
POINT NAME
OBJECT ID
AV:9
Active Demand Limit
AV:10
Air Temp Lvg Supply Fan
AV:11
CEM AN1 4-20 ma J5,1-2
AV:12
CEM AN1 10K temp J5,1-2
AV:13
CEM AN2 4-20 ma J5,3-4
AV:14
CEM AN2 10K temp J5,3-4
AV:15
Temper Supply Air Setpt
AV:16
BP PID Evaluation Time Level
AV:17
BP Setpoint Offset
AV:18
BP Threshold Adjustment
AV:22
Capacity Load Factor
AV:23
Capacity Threshold Adj
AV:24
Compressor A1 Run Hours
AV:25
Compressor A1 Starts
AV:26
Compressor A1 Strikes
AV:27
Compressor A1 Timeguard
AV:28
Compressor A2 Run Hours
AV:29
Compressor A2 Starts
AV:30
Compressor A2 Strikes
AV:31
Compressor A2 Timeguard
AV:32
Compressor B1 Run Hours
AV:33
Compressor B1 Starts
AV:34
Compressor B1 Strikes
AV:35
Compressor B1 Timeguard
AV:36
Compressor B2 Run Hours
AV:37
Compressor B2 Starts
AV:38
Compressor B2 Strikes
AV:39
Compressor B2 Timeguard
AV:40
Compressor Lockout Temp
AV:41
Cool Trend Demand Level
AV:42
Cool Trend Time (secs)
AV:43
Ctl.Temp RAT,SPT or ZONE
AV:44
Current Running Capacity
AV:45
DAQ PPM Fan Off Setpoint
AV:46
DAQ PPM Fan On Setpoint
AV:49
Dehumidify Cool Setpoint
AV:50
Dehumidify RH Setpoint
AV:52
Demand Limit Select
AV:53
Demand Limit Sw.1 Setpt.
AV:54
Demand Limit Sw.2 Setpt.
AV:56
Diff.Air Quality in PPM
AV:58
Diff. AQ Responsiveness
AV:59
Dmd Level(-) Low Cool OFF
AV:60
Dmd Level(-) Low Heat OFF
See legend on page 182.
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST
READ
UNITS
ONLY
W
R
W
W
W
W
W
W
W
in H2O
W
R
W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
W
W
W
R
R
W
W
W
W
W
W
W
R
W
W
W
DEFAULT
RANGE
VALUE
%
n/a
0-100
°F
n/a
n/a
mA
n/a
0-20
°F
n/a
-40-240
mA
n/a
0-20
°F
n/a
-40-240
°F
n/a
0-100
min
1
0-10
0.05
0-0.5
n/a
1
0.1-10
%
n/a
n/a
n/a
1
0-10
hr
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
hr
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
hr
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
hr
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
°F
40
-20-55
°^F
0.1
0.1-5
sec
120
30-600
°F
n/a
n/a
%
n/a
n/a
n/a
200
0-2000
n/a
400
0-2000
°F
45
40-55
%
55
10-90
n/a
0
0-3
%
80
0-100
%
50
0-100
n/a
n/a
n/a
n/a
0
-5-5
°^F
1
0.5-2
°^F
1
0.5-2
176
BACNET
UNIT
OBJECT NAME
POINT
dem_lim_1
DEM_LIM
sat_1
SAT
cem4201_1
CEM4201
cem10k1_1
CEM10K1
cem4202_1
CEM4202
cem10k2_1
CEM10K2
sasptemp_1
SASPTEMP
bpperiod_1
BPPERIOD
bpso_1
BPSO
bpz_gain_1
BPZ_GAIN
smz_1
SMZ
z_gain_1
Z_GAIN
hr_a1_1
HR_A1
cy_a1_1
CY_A1
cmpa1str_1
CMPA1STR
cmpa1_tg_1
CMPA1_TG
hr_a2_1
HR_A2
cy_a2_1
CY_A2
cmpa2str_1
CMPA2STR
cmpa2_tg_1
CMPA2_TG
hr_b1_1
HR_B1
cy_b1_1
CY_B1
cmpb1str_1
CMPB1STR
cmpb1_tg_1
CMPB1_TG
hr_b2_1
HR_B2
cy_b2_1
CY_B2
cmpb2str_1
CMPB2STR
cmpb2_tg_1
CMPB2_TG
oatlcomp_1
OATLCOMP
ctrendlv_1
CTRENDLV
ctrendtm_1
CTRENDTM
ctrltemp_1
CTRLTEMP
htsg_cap_1
HTSG_CAP
daqfnoff_1
DAQFNOFF
daqfnon_1
DAQFNON
dhcoolsp_1
DHCOOLSP
dhrelhsp_1
DHRELHSP
dmd_ctrl_1
DMD_CTRL
dlswsp1_1
DLSWSP1
dlswsp2_1
DLSWSP2
daq_1
DAQ
iaqreact_1
IAQREACT
dmdlcoff_1
DMDLCOFF
dmdlhoff_1
DMDLHOFF