Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 119

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

Table 116 — Economizer Control Board (ECB1) Inputs and Outputs
POINT
POINT DESCRIPTION
NAME
INPUTS
RMTIN
Remote occupancy
ECONENBL,
Economizer enable
ECOORIDE
RARH
Return air relative humidity
OARH
Outdoor air relative humidity
OUTPUTS
ECB1_AO1
ECB1, analog output 1
ECONOCMD Economizer actuator
(digital control)
PE_A
Power Exhaust stage A
PE_B
Power Exhaust stage B
PE_C
Power Exhaust stage C
ECON_PWR
Economizer Power
Fig. 27 — Economizer Control Board (ECB1) and VAV Control Board (ECB2)
I/O POINT
PLUG AND PIN
NAME
REFERENCE
DI1
J4, 1-2
DI2
J4, 3-4
AN1
J5, 1-3
AN2
J5, 4-6
AO1
J9, 1-2
PP/MP
J7, 1-3
RLY1
J8, 1-3
RLY 2
J8, 4-6
RLY 3
J8, 7-9
RLY 6
J8, 16-18
119
SIGNAL PIN(S)
2
4
1=24VDC, 2=0-20mA in, 3=GND
4=24VDC, 5=0-20mA in, 6=GND
1=0-20mA, 2=GND
1=PP/MP Data, 2=24VAC, 3=GND
1 = 2 = RLY1A, 3 = RLY1B
4 =5 = RLY2A, 6 = RLY2B
7 = 8 = RLY3A, 9 = RLY3B
16 = 17 = RLY6A, 18 = RLY6B
PORT STATE
24VAC = 1, 0VAC = 0
24VAC = 1, 0VAC = 0
0-20mA
0-20mA
0-20mA OUT
Belimo PP/MP Protocol
1 = Closes RLY1A/RLY1B
1 = Closes RLY2A/RLY2B
1 = Closes RLY3A/RLY3B
1 = Closes RLY6A/RLY6B
A48-7706