Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 142

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

ITEM
AIR.P
AIR PRESSURES
SP
Static Pressure
BP
Building Pressure
REF.P
REFRIGERANT PRESSURES
DP.A
Cir A Discharge Pressure
SP.A
Cir A Suction Pressure
DP.B
Cir B Discharge Pressure
SP.B
Cir B Suction Pressure
ITEM
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
UCSP
Unoccupied Cool Setpoint
GAP
Heat-Cool Setpoint Gap
V.C.ON
VAV Occ. Cool On Delta
V.C.OF
VAV Occ. Cool Off Delta
SASP
Supply Air Setpoint
SA.HI
Supply Air Setpoint Hi
SA.LO
Supply Air Setpoint Lo
SA.HT
Heating Supply Air Setpt
T.PRG
Tempering Purge SASP
T.CL
Tempering in Cool SASP
T.V.OC
Tempering Vent Occ SASP
T.V.UN
Tempering Vent Unocc. SASP
ITEM
GEN.I
GENERAL INPUTS
FLT.S
Filter Status Input
G.FAN
Fan Request From IGC
REMT
Remote Input State
E.SW
Economizer Control Input
E.ENA
Remote Economizer Enable
E.OVR
Econo Position Override
S.FN.S
Supply Fan Status Switch
DL.S1
Demand Limit Switch 1
DL.S2
Demand Limit Switch 2
DH.IN
Dehumidify Switch Input
FD.BK
COMPRESSOR FEEDBACK
CS.A1
Compressor A1 Feedback
CS.A2
Compressor A2 Feedback
CS.B1
Compressor B1 Feedback
CS.B2
Compressor B2 Feedback
STAT
THERMOSTAT INPUTS
G
Thermostat G Input
W1
Thermostat W1 Input
W2
Thermostat W2 Input
Y1
Thermostat Y1 Input
Y2
Thermostat Y2 Input
FIRE
FIRE-SMOKE INPUTS
FSD
Fire Shutdown Input
PRES
Pressurization Input
EVAC
Evacuation Input
PURG
Smoke Purge Input
REL.H
RELATIVE HUMIDITY
OA.RH
Outside Air Rel. Humidity
OA.EN
Outdoor Air Enthalpy
OA.DP
OutsideAir Dewpoint Temp
RA.RH
Return Air Rel. Humidity
RA.EN
Return Air Enthalpy
AIR.Q
AIR QUALITY SENSORS
IAQ.I
IAQ - Discrete Input
IAQ
IAQ - PPM Return CO2
OAQ
OAQ - PPM Return CO2
DAQ
Diff.Air Quality in PPM
IQ.P.O
IAQ Min.Pos. Override
RSET
RESET INPUTS
SA.S.R
Supply Air Setpnt. Reset
SP.RS
Static Pressure Reset
*The display text changes depending on the remote switch configuration (Configuration
Switch), then the display text will be "On" or "Off." If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be "Occupied" or
"Unoccupied." If RM.CF is set to 2 (Start/Stop), then the display text will be "Stop" or "Start." If RM.CF is set to 3 (Override Switch), then the display
text will be "No Override" or "Override."
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — PRESSURES
EXPANSION
MODE — SET POINTS
DESCRIPTION
EXPANSION
DRTY/CLN
ON/OFF
*
YES/NO
YES/NO
YES/NO
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ALARM/NORMAL
ALARM/NORMAL
ALARM/NORMAL
ALARM/NORMAL
HIGH/LOW
RANGE
UNITS
"H2O
"H2O
PSIG
PSIG
PSIG
PSIG
RANGE
UNITS
40-99
dF
40-99
dF
40-99
dF
40-99
dF
2-10
^F
0-25
^F
1-25
^F
45-75
dF
45-75
dF
45-75
dF
80-120
dF
–20-80
dF
5-75
dF
–20-80
dF
–20-80
dF
MODE — INPUTS
RANGE
UNITS
%
dF
%
%
^F
142
CCN POINT
WRITE STATUS
SP
BP
DP_A
SP_A
DP_B
SP_B
CCN POINT
OHSP
OCSP
UHSP
UCSP
HCSP_GAP
VAVOCON
VAVOCOFF
SASP
SASP_HI
SASP_LO
SASPHEAT
TEMPPURG
TEMPCOOL
TEMPVOCC
TEMPVUNC
CCN POINT
WRITE STATUS
FLTS
forcible
IGCFAN
RMTIN
forcible
ECOSW
forcible
ECONENBL
forcible
ECOORIDE
forcible
SFS
forcible
DMD_SW1
forcible
DMD_SW2
forcible
DHDISCIN
forcible
CSB_A1
CSB_A2
CSB_B1
CSB_B2
G
forcible
W1
forcible
W2
forcible
Y1
forcible
Y2
forcible
FSD
forcible
PRES
forcible
EVAC
forcible
PURG
forcible
OARH
forcible
OAE
OADEWTMP
RARH
forcible
RAE
IAQIN
forcible
IAQ
forcible
OAQ
forcible
DAQ
IAQMINOV
forcible
SASPRSET
forcible
SPRESET
forcible
UNIT
RM.CF). If RM.CF is set to 0 (No Remote
DEFAULT
68
75
55
90
5
3.5
2
55
55
60
85
50
5
65
50