Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

TABLE
COOL
Capacity Threshold Adjust
Compressor Lockout Temp
Fan-off Delay, Mech Cool
Minimum Load Valve?
Motor Master Control ?
Head Pressure Setpoint
Enable Compressor A1
Enable Compressor A2
Enable Compressor B1
Enable Compressor B2
CSB A1 Feedback Alarm
CSB A2 Feedback Alarm
CSB B1 Feedback Alarm
CSB B2 Feedback Alarm
Rev. Rotation Verified ?
Hi SST Alert Delay Time
DEHU
Dehumidification Config
Dehumidification Sensor
Econ disable in DH mode?
Vent Reheat Setpt Select
Vent Reheat RAT offset
Vent Reheat Setpoint
Dehumidify Cool Setpoint
Dehumidify RH Setpoint
DISP
Metric Display
Language Selection
Password Enable
Service Password
Contrast Adjustment
Brightness Adjustment
DLVT
Dmd Level
Lo Heat On
Dmd Level(+) Hi Heat On
Dmd Level(-) Lo Heat Off
Dmd Level
Lo Cool On
Dmd Level(+) Hi Cool On
Dmd Level(-) Lo Cool Off
Cool Trend Demand Level
Heat Trend Demand Level
Cool Trend Time
Heat Trend Time
DMDL
Demand Limit Select
Demand Limit at 20 ma
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Sw.1 Setpt.
Demand Limit Sw.2 Setpt.
ECON
Economizer Installed ?
Economizer Min.Position
Economizer Max.Position
Economzr trim for sumZ ?
Econ ChangeOver Select
OA Enthalpy ChgOvr Selct
Outdr.Enth Compare Value
High OAT Lockout Temp
OA Dewpoint Temp Limit
Outside Air RH Sensor
Economizer Control Type
Economizer Switch Config
Economizer Prop.Gain
Economizer Range Adjust
Economizer Speed Adjust
Economizer Deadband
Unoc Econ Free Cool Cfg
Unoc Econ Free Cool Time
Un.Ec.Free Cool OAT Lock
EDTR
EDT Reset Configuration
Reset Ratio
Reset Limit
EDT 4-20 ma Reset Input
APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
NAME
–10 -> 10
–20 -> 55
0-600
Yes/No
Yes/No
80-150
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Yes/No
5-30
0-2
1-2
Yes/No
0-1
0-8
55-95
40-55
10-90
Off/On
0-1
Enable/Disable
0000-9999
–255 - 255
–255 - 255
–1 - 2
0.5 - 20.0
0.5 - 2
–1 - 2
0.5 - 20.0
0.5 - 2
0.1 - 5
0.1 - 5
30 - 600
30 - 600
0 - 3
0 - 100
0 - 99
0 - 60
0 - 120
0 - 100
0 - 100
Yes/No
0 - 100
0 - 100
Yes/No
0 - 3
1 - 5
18 - 28
55 - 120
50 - 62
Enable/Disable
1-3
0-2
0.7 - 3.0
0.5 - 5
0.1 - 10
0.1 - 2
0-2
0-720
40-70
0 - 3
0 - 10
0 - 20
Enable/Disable
RANGE
UNITS
dF
sec
dF
min
^F
dF
dF
%
^F
^F
^F
^F
^F
^F
^F
^F
sec
sec
%
%
min
%
%
%
%
dF
dF
^F
^F
min
dF
^F
153
POINT NAME
DEFAULT
Z_GAIN
1
OATLCOMP
40
COOL_FOD
60
MLV_SEL
No
MOTRMAST
No
HPSP
110
CMPA1ENA
Enable
CMPA2ENA
Enable
CMPB1ENA
Enable
CMPB2ENA
Enable
CSB_A1EN
Enable
CSB_A2EN
Enable
CSB_B1EN
Enable
CSB_B2EN
Enable
REVR_VER
No
HSSTTIME
10
DHSELECT
0
DHSENSOR
1
DHECONEN
No
DHVHTCFG
0
DHVRAOFF
0
DHVHT_SP
70
DHCOOLSP
45
DHRELHSP
55
DISPUNIT
Off
LANGUAGE
0
PASS_EBL
Enable
PASSWORD
1111
CNTR_ADJ
0
BRTS_ADJ
0
DMDLHON
1.5
DMDHHON
0.5
DMDLHOFF
1
DMDLCON
1.5
DMDHCON
0.5
DMDLCOFF
1
CTRENDLV
0.1
HTRENDLV
0.1
CTRENDTM
120
HTRENDTM
120
DMD_CTRL
0
DMT20MA
100
SHED_NUM
0
SHED_DEL
0
SHED_TIM
60
DLSWSP1
80
DLSWSP2
50
ECON_ENA
Yes
ECONOMIN
20
ECONOMAX
98
ECONTRIM
Yes
ECON_SEL
1
OAEC_SEL
2
OAEN_CFG
24
OAT_LOCK
60
OADEWCFG
55
OARHSENS
Disable
ECON_CTL
1
ECOSWCFG
0
EC_PGAIN
1
EC_RANGE
2.5
EC_SPEED
0.75
EC_DBAND
0.5
UEFC_CFG
0
UEFCTIME
120
UEFCNTLO
50
EDRSTCFG
0
RTIO
2
LIMT
10
EDTRSENS
Disable