Carrier WEATHERMAKER 48/50AJ Operation And Service Manual page 154

Single package large rooftop units with comfortlink version 5.x controls
Table of Contents

Advertisement

TABLE
HEAT
Heating Control Type
Heating Supply Air Setpt
Occupied Heating Enabled
MBB Sensor Heat Relocate
Fan-off Delay, Gas Heat
Fan-off Delay, Elec Heat
Staged Gas Heat Type
Max Cap Change per Cycle
S.Gas DB min.dF/PID Rate
St.Gas Temp. Dead Band
Heat Rise dF/sec Clamp
LAT Limit Config
Heat Control Prop. Gain
Heat Control Derv. Gain
Heat PID Rate Config
IAQ_
Economizer Min.Position
IAQ Demand Vent Min.Pos.
IAQ Analog Sensor Config
IAQ 4-20 ma Fan Config
IAQ Discrete Input Config
IAQ Disc.In. Fan Config
OAQ 4-20ma Sensor Config
IAQ Econo Override Pos.
Diff.Air Quality LoLimit
Diff. Air Quality HiLimit
DAQ PPM Fan Off Setpoint
DAQ PPM Fan On Setpoint
Diff. AQ Responsiveness
OAQ Lockout Value
User determined OAQ
IAQ Low Reference
IAQ High Reference
OAQ Low Reference
OAQ High Reference
IAQ Purge
IAQ Purge Duration
IAQ Purge LoTemp Min Pos
IAQ Purge HiTemp Min Pos
IAQ Purge OAT Lockout
SP__
Static Pres.VFD Control?
Static Pres.Fan Control?
Static Pressure Sensor
Static Press. Low Range
Static Press. High Range
Static Pressure Setpoint
VFD Minimum Speed
VFD Maximum Speed
VFD Fire Speed Override
Stat. Pres. Reset Config
SP Reset Ratio ("/dF)
SP Reset Limit in iwc(")
SP Reset Econo.Position
Stat.Pres.PID Run Rate
Static Press. Prop. Gain
Static Pressure Intg. Gain
Static Pressure Derv. Gain
Static Press.System Gain
TRIM
Air Temp Lvg SF Trim
RAT Trim
OAT Trim
SPT Trim
Cir A Sat.Cond.Temp Trim
Cir B Sat.Cond.Temp Trim
Suct.Press.Circ.A Trim
Suct.Press.Circ.B Trim
Dis.Press.Circ.A Trim
Dis.Press.Circ.B Trim
Static Press. Trim (ma)
Bldg. Pressure Trim (ma)
APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
NAME
0 - 4
80-120
Yes/No
Yes/No
45-600
10-600
0 - 4
5 - 45
0 - 5
0 - 5
0.05 - 0.2
0 - 20
0 - 1.5
0 - 1.5
60 - 300
0 - 100
0 - 100
0 - 4
0 - 2
0 - 2
0 - 2
0 - 2
0 - 100
0 - 1000
100 - 2000
0 - 2000
0 - 2000
–5 - 5
0 - 2000
0-5000
0 - 5000
0 - 5000
0 - 5000
0 - 5000
Yes/No
5-60
0-100
0-100
35-70
No
Yes
Enable/Disable
–10 - 0
0 - 10
0 - 5
10 - 50
50 - 100
0 - 100
0-4 (multi-text strings)
0 - 2.00
0 - 2.00
0 - 100
1 - 200
0 - 100
0 - 50
0 - 50
0 - 50
–10 - 10
–10 - 10
–10 - 10
–10 - 10
–30 - 30
–30 - 30
–50 - 50
–50 - 50
–50 - 50
–50 - 50
–2 - 2
–2 - 2
RANGE
UNITS
dF
^F
^F
sec
%
%
%
min
%
%
dF
"H2O
%
%
%
%
sec
^F
^F
^F
^F
^F
^F
PSI
PSI
PSI
PSI
154
POINT NAME
DEFAULT
HEATTYPE
0
SASPHEAT
85
HTOCCENA
No
HTLATMON
No
GAS_FOD
45
ELEC_FOD
30
HTSTGTYP
0
HTCAPMAX
45
HT_MR_DB
0.5
HT_SG_DB
2
HTSGRISE
0.06
HTLATLIM
10
HT_PGAIN
1
HT_DGAIN
1
HTSGPIDR
90
ECONOMIN
5
IAQMINP
0
IAQANCFG
0
IAQANFAN
0
IAQINCFG
0
IAQINFAN
0
OAQANCFG
0
IAQOVPOS
100
DAQ_LOW
100
DAQ_HIGH
700
DAQFNOFF
200
DAQFNON
400
IAQREACT
0
OAQLOCK
0
OAQ_USER
400
IAQREFL
0
IAQREFH
2000
OAQREFL
0
OAQREFH
2000
IAQPURGE
No
IAQPTIME
15
IAQPLTMP
10
IAQPHTMP
35
IAQPNTLO
50
STATICFG
No
STATPFAN
Yes
SPSENS
Disable
SP_LOW
0
SP_HIGH
5
SPSP
1.5
STATPMIN
20
STATPMAX
100
STATPFSO
100
SPRSTCFG
0
SPRRATIO
0.2
SPRLIMIT
0.75
ECONOSPR
5
SPIDRATE
2
STATP_PG
20
STATP_IG
2
STATP_DG
0
STATP_SG
1
SAT_TRIM
0
RAT_TRIM
0
OAT_TRIM
0
SPT_TRIM
0
SCTATRIM
0
SCTBTRIM
0
SPA_TRIM
0
SPB_TRIM
0
DPA_TRIM
0
DPB_TRIM
0
SPMATRIM
0
BPMATRIM
0