Power Supply For Instantaneous Heating Water Heater (Only Type Awb-Ac); Power Supply With Power-Off: Without On-Site Load Disconnect - Viessmann Vitocal 200-S Installation And Service Instructions Manual

Air source heat pump, split version for heating and cooling operation
Table of Contents

Advertisement

Power supply
(cont.)

Power supply for instantaneous heating water heater (only type AWB-AC)

Internal unit
1/N/PE
230 V/50 Hz
A
L1
L1
L1
N
B
N
N
3/N/PE
400 V/50 Hz
A
L3
L2
L1
B
N
N
Fig. 37
Internal unit wiring chamber (see chapter "Over-
A
view of connections":" Internal unit")
Jumpers
B

Power supply with power-OFF: Without on-site load disconnect

The power-OFF signal is connected directly to the heat
pump control unit; with heat pump cascades the con-
nection is only made at the lead heat pump.
Parameter "Output for instant. heating water heater
at power-OFF 790A" determines whether and at what
stage an instantaneous heating water heater (if instal-
led) remains operational during power-OFF.
Note
Observe the technical connection conditions of the rel-
evant power supply utility.
Recommended power cable:
2
400 V~: 5 x 2.5 mm
2
230 V~: 7 x 2.5 mm
Fuse rating max. 16 A
Economy tariff and power-OFF can be used
Installation sequence