Installation sequence

Electrical connection

Danger
Damaged wiring insulation wiring can lead to
serious injury from electrical current and result in
appliance damage.
Route cables so that they cannot touch very hot,
vibrating or sharp-edged components.
Danger
Incorrect wiring can lead to serious injury from
electrical current and result in appliance dam-
age.
Take the following measures to prevent drifting
of wires into the adjacent voltage area:
Route LV leads < 42 V separately from cables
42 V/230 V~/400 V~ and secure with cable
>
ties.
Only strip the minimum of insulation from
cables as close as possible to the terminals
and bundle tightly to the corresponding termi-
nals.
If 2 components are connected to the same
terminal, press both cores together in a single
wire ferrule.
22
Danger
In terms of safety, the BUS cables for the inter-
nal/external units (12 V or 43 V) do not count as
LV leads. In the event of certain errors, these
BUS cables may still carry a mains voltage.
Contact with the BUS cables can lead to serious
injury from electric current.
The BUS cables must be routed together with
the 230 V cables.
Note
Make all connections on the control panel, (see
page 24) with flexible cables to ensure that the con-
trol panel can be placed in the service position (see
page 61).