Installation sequence
Installing the internal unit
Transport
!
Please note
Impacts, compression and tensile loads can
cause damage to the outside panels of the
appliance.
Never apply loads/weight to the top, front or
side panels of the appliance.
Installation room requirements
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
■
The installation room must be dry and free
from the risk of frost.
■
Ensure ambient temperatures between 0 and
35 °C.
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
Minimum clearances
A
B
100
Fig. 8
Cable entry <42 V
A
Cable entry 400 V~/230 V~,
B
14
100
42 V
>
Minimum room volume (to EN 378):
Type AWB/AWB-AC Minimum room volume in m
201.B04
201.B05
201.B07
201.B10
201.B13
201.C10
201.C13
201.C16
3
2.7
4.8
4.8
6.7
6.7
6.7
6.7
6.7