Commissioning the system
Parameters
Vitocom 100, type GSM/GSM2
"System definition"
Ó
"Vitocom 100 7017"
External extension
"System definition"
Ó
"External extension 7010"
Parameters for external functions
Parameter
External demand
If applicable "Internal hydraulics"
"Flow temperature for external demand 730C"
External starting of the compressor; mixer in control mode or OPEN
"System definition"
Ó
"Effect of external demand on heat pump/heating circuits
7014"
External changeover of the operating status of various system components
"System definition"
Ó
"System components for external changeover 7011"
"Operating status for external changeover 7012"
"Duration of external changeover 7013"
External blocking of compressor and pumps
"System definition"
Ó
"Effect of external blocking on pumps/compressor 701A"
External blocking of the compressor; mixer in control mode or CLOSED
"System definition"
Ó
"Effect of ext. blocking on heat pump/heating circuits 7015"
"Effect of external blocking on pumps/compressor 701A"
Type AWB-AC: Cooling function parameters
Parameters
"Cooling"
Ó
"Cooling function 7100"
"Cooling circuit 7101"
(cont.)
Ó
Commissioning, inspection, maintenance
Setting
"1"
"1" EA1 extension
"2" AM1 extension
"3" EA1 and AM1 extensions
Note
Parameters for external functions: See
the following table.
Setting
Set flow temperature for external de-
mand
"0" to "7"
(Observe parameter "Flow tempera-
ture for external demand 730C")
"0" to "127"
"0" to "3"
"0" to "12"
"0" to "31"
"0" to "8"
"0" to "31"
Setting
"3"
"1" Heating circuit A1/HC1
"2" Heating circuit M2/HC2
"4" Separate cooling circuit SKK
55