Installation sequence
Power supply
(cont.)
Heat pump control unit power supply 230 V~
X3
X2
6
7
8
9
16
16
18
F1 T6,3AH
L1
N
Fig. 24
Compressor power supply 400 V~
L1
L2
3/N/PE
L3
400 V/50 Hz
N
Fig. 25
■
Fuse protection in accordance with the compressor
rating (see "Specification").
■
Economy tariff and power-OFF can be applied.
Compressor power supply 230 V~
L1
230 V / 50 Hz
N
1/N/PE
?
Fig. 26
■
MCB/fuse protection according to compressor out-
put: See "Specification".
Economy tariff and power-OFF can be applied
■
Connecting 400 V~ instantaneous heating water heater power supply
400 V / 50 Hz
3/N/PE
L3
L3
L2
L2
L1
L1
PE
PE
N3
N2
N
N1
Fig. 27
30
X1
N
N
3
1
1
L1
L2
L3
N
PE
L1
N
PE
Note
This supply must never be blocked.
■
Max. fuse rating 16 A
■
Standard tariff (no economy tariff with power-OFF
possible)
■
Recommended power cable: 3 x 1.5 mm
2
(5 x 1.5 mm
with power-OFF)
■
No parameters need to be set when using economy
tariff with power-OFF. The compressor is shut down
during the power-OFF time.
Recommended power cable:
■
2
5 x 2.5 mm
Max. cable length:
25 m
■
No parameters need to be set when using economy
tariff with power-OFF. The compressor is shut down
during the power-OFF time.
■
Recommended power cable:
2
3 x 4 mm
Max. cable length: 25 m
■
Max. fuse rating 16 A: See "Specification".
■
Economy tariff and power-OFF can be applied
■
Recommended power cable:
5 x 2.5 mm
2
Max. cable length: 25 m
2