Power supply
(cont.)

Connecting the power cable of the instantaneous heating water heater (only type AWB-AC)

Internal unit
1/N/PE
230 V/50 Hz
A
L1
L1
L1
N
B
N
N
3/N/PE
400 V/50 Hz
A
L3
L2
L1
B
N
N
Fig. 25
Internal unit wiring chamber (see chapter "Over-
A
view of connections":" Internal unit")
B
Jumpers

Power supply with power-OFF

Power-OFF without on-site load disconnection
The power-OFF signal is connected directly to the heat
pump control unit; with heat pump cascades the con-
nection is only made at the lead heat pump.
Parameter "Output for instant. heating water heater
at power-OFF 790A" determines whether and at what
stage an instantaneous heating water heater (if instal-
led) remains operational during power-OFF.
Recommended power cable:
2
400 V~: 5 x 2.5 mm
2
230 V~: 7 x 2.5 mm
Fuse rating max. 16 A
Economy tariff and power-OFF can be used
Note
Observe the technical connection conditions of the rel-
evant power supply utility.
Installation sequence