Internal Unit: Luster Terminals (Signal And Safety Connections) - Viessmann Vitocal 200-S Installation And Service Instructions Manual

Air source heat pump, split version for heating and cooling operation
Table of Contents

Advertisement

Electrical connection

Internal unit: Luster terminals (signal and safety connections)

Set the required parameters during commissioning:
See from page 50.
Terminals
Function
X3.1
Switched phase
X3.3
Flow switch
X3.4
X3.6
Power-OFF (jumper fitted at the fac-
X3.7
tory)
G
(cont.)
Explanation
Via control unit ON/OFF switch
Note
Observe the total load 1000 W of all connected compo-
nents.
Requires floating N/O contact:
Closed: Heat pump in operation
Open: Heat pump shut down
Breaking capacity 230 V~, 0.15 A
Remove jumper when connecting.
Requires floating N/C contact:
Closed: Heat pump in operation
Open: Heat pump shut down
Breaking capacity 230 V~, 0.15 A
Remove jumper when connecting.
Note
No parameters need to be set.
The compressor is "forced" off as soon as the contact
opens.
The power-OFF contact signal switches off the supply
voltage to the relevant function components, subject
to power supply utility.
For the instantaneous heating water heater, the
stages to be switched off can be selected (parameter
"Output for Instant.htg wtr heater at power-OFF
790A").
The power supply for the heat pump control unit
(3 x 1.5 mm
2
) and the cable for the power-OFF signal
can be combined in a single 5-core cable.
With heat pump cascades
Power supply without on-site load disconnect:
Only connect the power-OFF signal to the lead heat
pump: See page 37.
Power supply with on-site load disconnect: Con-
nect the power-OFF signal to each heat pump: See
page 38.
Further information on power-OFF: See chapter
"Power supply".
In connection with Smart Grid:
Do not connect the power-OFF signal.
Do not remove jumper.
Installation sequence
29

Advertisement

Table of Contents
loading

Table of Contents