Checking Electrical Connections Of The Internal Unit For Firm Seating 11. Checking The Condensate Connection To The External Unit; Checking The Free Running Of The Fan In The External Unit; Cleaning The Heat Exchanger In The External Unit - Viessmann Vitocal 200-S Installation And Service Instructions For Contractors

Air/water heat pump, split version for heating and cooling operation
Table of Contents

Advertisement

Further details regarding the individual steps
Checking the condensate connection to the external unit
Check that the condensate connection
can freely drain:
■ Contamination of the condensate pan
and condensate line
■ Condensate line without any kinks

Checking the free running of the fan in the external unit

Danger
Starting the fan with the external
unit open can lead to severe inju-
ries.
Isolate the external unit from the
power supply and safeguard
against reconnection.
Be aware that the fan may run
on.

Cleaning the heat exchanger in the external unit

Danger
Contact with 'live' components
and their contact with water can
lead to severe injury from electric
shock.
Isolate the external unit from the
power supply and safeguard
against reconnection.
Be aware that the fan may run
on.
Cleaning with compressed air
1. Open the casing of the external unit.
!
Please note
The sharp edges of the heat
exchanger can result in inju-
ries.
Avoid contact.
Commissioning, inspection, maintenance
(cont.)
1. ■ Type AWS/AWS-AC 104:
First remove the top cover and then
the front panel.
■ Type AWS/AWS-AC 107, 110,
113:
Remove the air outlet grille from the
external unit.
2. Turn the fan by hand.
!
2.
Please note
Excessive air pressure from
the front and sides can result
in the deformation of the alu-
minium fins of the heat
exchanger.
Only point the compressed air
gun at the heat exchanger
from the front and at an ade-
quate distance.
Blow out the heat exchanger from
the inside out with compressed air.
3. Check the aluminium fins of the heat
exchanger for deformation and
scratches; if required repair with a
suitable tool (e.g. fin comb).
4. Close the casing of the external unit.