Indoor Unit: Luster Terminals (Signal And Safety Connections) - Viessmann Vitocal 200-A Installation And Service Instructions Manual

Hide thumbs Also See for Vitocal 200-A:
Table of Contents

Advertisement

Electrical connection
Plug
sXG
Terminals
Function
225.1
Heating circuit pump of the heating
circuit with mixer M2/HC2
M2
r
225.2
Mixer motor control, heating circuit
M2/HC2
M2
Signal mixer CLOSE
225.3
Mixer motor control, heating circuit
M2/HC2
M2
Signal mixer OPEN

Indoor unit: Luster terminals (signal and safety connections)

Set the required parameters during commissioning:
See page 62 onwards.
Terminals
Function
X3.1
Switched phase
X3.6
Power-OFF (jumper fitted at the fac-
X3.7
tory)
G
(cont.)
Explanation
Connect a temperature limiter to restrict the maximum
temperature for underfloor heating circuits (if installed)
in series.
Connection values:
Output: 100 W
Voltage: 230 V~
Max. control current: 4(2) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. control current: 0.2(0.1) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. control current: 0.2(0.1) A
Explanation
Via control unit ON/OFF switch
Note
Observe the total load 1000 W of all connected compo-
nents.
Requires floating contact:
Closed: Heat pump operational
Open: Heat pump shut down
Breaking capacity 230 V~, 0.15 A
Remove jumper when connecting.
Note
No parameters need to be set
The compressor is "forced" off as soon as the contact
opens.
The power-OFF signal switches off the power supply
to the relevant components, subject to the power sup-
ply utility.
For the instantaneous heating water heater, the
stages to be switched off can be selected (parameter
"Output for instant. heating water heater at pow-
er-OFF 790A").
The power supply for the heat pump control unit
2
(3 x 1.5 mm
) and the cable for the power-OFF signal
can be combined in a single 5-core cable.
Installation sequence
39