Indoor Unit: Luster Terminals (Signal And Safety Connections) - Viessmann Vitocal 200-S Installation And Service Instructions For Contractors

Air/water heat pump, split version for heating and cooling operation
Table of Contents

Advertisement

Installation sequence
Electrical connection

Indoor unit: luster terminals (signal and safety connections)

Set the required parameters during commissioning:
see page 51 onwards.
Terminals
Function
X3.1
Switched phase
X3.3
Flow switch
X3.4
X3.6
Power-OFF (jumper fitted at the fac-
X3.7
tory)
G
30
(cont.)
Explanation
Via control unit ON/OFF switch
Note
Observe the total load 1000 W of all connected compo-
nents.
Requires floating N/O contact:
Closed: heat pump operational
Open: heat pump shut down
Breaking capacity 230 V~, 0.15 A
Remove jumper when connecting.
Requires floating N/C contact:
Closed: heat pump operational
Open: heat pump shut down
Breaking capacity 230 V~, 0.15 A
Remove jumper when connecting.
Note
No parameters need to be set.
The compressor is "forced" off as soon as the contact
opens.
The power-OFF contact signal switches off the power
supply to the relevant components, subject to the
power supply utility.
For the instantaneous heating water heater, the
stages to be switched off can be selected (parameter
"Output for instant. heating water heater at pow-
er-OFF 790A").
The power supply for the heat pump control unit
(3 x 1.5 mm
2
) and the cable for the power-OFF signal
can be combined in a single 5-core cable.
With heat pump cascades
Power supply without on-site load disconnec-
tion: Only connect the power-OFF signal to the
lead heat pump: see page 38.
Power supply with on-site load disconnection:
Connect the power-OFF signal to all heat pumps:
see page 39.
For further information regarding power-OFF: see
chapter "Power supply".
In connection with Smart Grid:
Do not connect the power-OFF signal.
Do not remove jumper.