17.4.2 Setting Parameter Control Area

This is the area to write the setting values of the positioning parameters and positioning data in the
shared memory into FROM(Flash memory), or to execute the recalculation of the positioning data.
The number of writing to FROM in the positioning unit is announced to the CPU through this area, and
writing the positioning parameters and positioning data in the shared memory to FROM is requested.
Also, the recalculation starting table number is set to recalculate the positioning data in the standard
area.
Offset
Bank
Name
address
Annunciation of
080H
number of
writing to FROM
Request for
081H
writing to FROM
00H
Recalculation
085H
starting table
number

17.4.3 Operation Speed Rate Area

Offset
Bank
Name
address
Operation speed
00H
088H
rate
Descriptions
Announces the number of writing the
positioning parameters and data in the
shared memory into FROM.
When writing into FROM by Configurator
PM, the following procedures will be
automatically performed.
When writing into FROM by ladder
programs, it is necessary to achieve the
following Configurator PM operation by
the ladder programs.
1. Write 5555H in this area by the ladder
program.
2. The positioning unit checks 5555H,
and write 6666H over in the same
area.
3. Check 6666H by the ladder program,
and write AAAAH over.
(Time out of 6666H is 30 seconds.)
4. The positioning unit copies the content
of the shared memory into FROM.
5. The positioning unit checkes writing.
When OK: The unit sets 0000H.
When NG: The unit sets FFFFH.
6. When confirming 0000H by the ladder
program, the operation will be
completed successfully. When
confirming FFFFH, an error will occur.
In that case, write 0000H over in this
area.
When the recalculation request signal
(Y87 contact) turns on, the positioning
unit will recalculate the positioning data
of all the axes from this table number to
No. 600.
Descriptions
All operations relating to axes
(positioning, JOG, home return) can be
perfomred at the specified rate.
The unit is %, and can be input in the
range of 1 to 100 (%).
Default
Setting
Unit
value
range
0
-
times
0000H
-
-
1
1 to 600
-
Default
Setting
Unit
value
range
100
1 to 100
%