Table 10: Menus and Submenus (Part 7 of 8)
Level 1
Level 2
(LCD Screen Name)
System Status
Changeover State
(Cont)
Zone Temp Source
Control Status
Cooling % Command
Heating % Command
Reheat % Command
Cool Stage 1
Heat Stage 1
Reheat Stage 1
Fan % Command
Fan
Controller Info
Model Name
Software Version
Unit Name
Device Name
Device Description
Commissioning
Supply Air Temperature
Heat Command
Cool Command
Supply Fan
Aux
Update
View Version
Load Firmware
Restore
Backup
TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Level 3
(Default Values)
Supply
Temperature
Unreliable
Internal Sensor
0%
0%
0%
Off
Off
Off
0%
On
TEC302x-xx
x.x.x.xxxx
TECxxxxx
TEC3000
Display Current
Temperature
0%
0%
No
No
x.x.x.xxxx
Capability Installation Instructions
39
1
Available Values
Changeover Disabled
Cooling Mode
Heating Mode
Supply Temperature Unreliable
Unreliable
Internal Sensor
Remote Sensor
Network Override
Input Not Installed
0 to 100%
0 to 100%
0 to 100%
On or Off
On or Off
On or Off
0 to 100%
On or Off when Supply Fan Type =
Single-speed or Variable-speed
Off, Low, Medium, or High when Supply
Fan Type = Multi-speed
User-Supplied
0 to 100%
0 to 100%
Yes or No
Yes or No
Current Release of Software
File list from USB drive
File list from USB drive or local storage*
*Configuration can be backed up to the
USB drive and restored to like models in
the effort to expedite the commissioning
process.
File list from USB drive or local storage*
*Configuration can be backed up to the
USB drive and restored to like models in
the effort to expedite the commissioning
process.