Configuring The Supply Fan - Fan Coil Only - Johnson Controls TEC3010 Installation Instructions Manual

Tec3000 series wireless proportional fan coil and individual zone thermostat controllers with dehumidification capability
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Note: Selecting VAV reboots the controller in order to apply the change.

Configuring the Supply Fan - Fan Coil Only

On fan coil units (2-pipe or 4-pipe), three different types of supply fans are supported. These are single-speed fan,
multi-speed fan (up to three discrete speeds), and VSF using a 0 to 10V control signal and an optional binary on/off
command. Note that fan control is not available when in VAV mode. To select the fan type:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Supply Fan.
4. Press Supply Fan Type and select Single Speed, Multi-Speed, or Variable Speed.
5. Press
to save and
For multi-speed fan control, you can adjust the point when the medium or high speed turns. The fan speed is based
on the load on the cooling or heating device, and is a percentage between 0 and 100. By default, the Med Speed
On Cmd is 33% and the High Speed On Cmd is 66%. When only two fan speeds are used, you must set the High
Speed On Cmd to 100% to disable the third speed, and set the Med Speed On Cmd to 50%. To adjust these
values:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Supply Fan.
4. Press Medium Speed On Cmd and adjust accordingly.
5. Press
to save and
6. Press High Speed On Cmd and adjust accordingly.
7. Press
to save and
For VSF control, the output is configurable for any range between 0 V and 10 V. The parameters are Start Voltage,
Full Speed Voltage, and Minimum Command. Start Voltage is the voltage output at which the fan begins running,
and Full Speed Voltage is the voltage output at which the fan reaches full speed. Minimum Command is the
percentage of the range between the Start Voltage and the Full Speed Voltage. The fan does not go below the
minimum command when the fan is turned on. By default, the Start Voltage is 2 V, the Full Speed Voltage is 10 V,
and the Minimum Command is 20%.
When the variable speed fan is off, the FAN binary output is off, and the voltage at the VSF output is 0 V. When the
fan turns on, the FAN binary output turns on, and the voltage at the VSF output begins controlling the fan. When
the VSF is configured for reverse acting mode (Start Voltage is above Full Speed Voltage), the VSF output goes to
the lesser of 10 V and 1 V above the Start Voltage when the fan is turned off.
To configure the variable speed parameters:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Supply Fan.
4. Press Start Voltage and adjust accordingly.
5. Press
to save and
6. Press Full Speed Voltage and adjust accordingly.
TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
to return to the previous screen.
to return to the previous screen.
to return to the previous screen.
to return to the previous screen.
Capability Installation Instructions
19

Hide quick links:

Advertisement

Table of Contents
loading