Setting The Control Mode; Setting The Fan Mode - Fan Coil Only - Johnson Controls TEC3010 Installation Instructions Manual

Tec3000 series wireless proportional fan coil and individual zone thermostat controllers with dehumidification capability
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

7. Press
to save and
8. Press Minimum Command and adjust accordingly.
9. Press
to save and

Setting the Control Mode

The Control Mode informs the controller to either run in Cooling only mode, Heating only mode, or Automatic mode
based on the temperature in the zone relative to the heating and cooling setpoints. Control Mode does not override
equipment lockouts or changeover. To set the Control Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Control Mode and select Cooling, Heating, or Auto.
5. Press
to save and

Setting the Fan Mode - Fan Coil Only

The Fan Mode informs the controller how to handle the fan. You can configure the fan using one of two options: a
Fan Mode available to the installer through the menu system, and a fan override available as an option to the end
user from the Fan icon on the home screen. See Customizing the Home Screen for information on enabling or
disabling end-user controls. The Fan Mode available to the installer is dependent on the fan type. The following
options are provided for single-and variable-speed fans:
On—Fan is continuously on.
Auto—Fan cycles on demand with the controller entering cooling, heating, or dehumidification modes.
Smart—Fan cycles on demand with the controller entering cooling or heating modes during unoccupied
periods but is continuously running during occupied and standby periods.
The following Fan Mode options are provided for multi-speed fans:
Low—Fan is continuously on low
Medium—Fan is continuously on medium
High—Fan is continuously on high
Auto—Fan cycles on demand with the controller entering cooling, heating, or dehumidification modes
Smart—Fan cycles on demand with the controller entering cooling or heating modes during unoccupied
periods but is continuously running during occupied and standby periods
The Fan Override icon on the home screen is dependent on the fan type. The following options are provided for
single- and variable-speed fans:
On—Overrides the fan to be continuously on.
Auto—Follows the behavior set as Fan Mode.
Quiet—Follows the behavior set as Fan Mode, but prevents the fan from ever going above minimum speed.
The Quiet option has no effect on equipment with single-speed fans.
The following Fan Override options are provided for multi-speed fans:
Low—Fan is continuously on low
Medium—Fan is continuously on medium
TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
to return to the previous screen.
to return to the previous screen.
to return to the previous screen.
Capability Installation Instructions