Table 10: Menus and Submenus (Part 5 of 8)
Level 1
Level 2
(LCD Screen Name)
Network Setup
FC Comm Mode
BACnet Instance ID*
BACnet Device Address*
BACnet Encoding Type
BACnet/MSTP Communication Mode
Pan ID
Equipment Setup
General
Unit Type
Valve Open Voltage
Valve Closed Voltage
Unoccupied Off Delay
Supply Fan
Supply Fan Type*
Start Voltage*
Full Speed Voltage*
Min Command*
Med Fan Speed On Cmd*
High Fan Speed On Cmd*
Reheat
Reheat Installed
Reheat Min Damper Position*
Reheat Fan Required*
Reheat Min On Time*
Reheat Min Off Time*
Changeover
Changeover Mode*
Supply Temp Type*
Changeover Setpoint*
TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Level 3
(Default Values)
Wireless Field Bus
1
4
ISO 10646
(UCS-2)
65535
4-Pipe
10 VDC
0 VDC
10 minutes
Single Speed
2 VDC
10 VDC
20%
33%
66%
No
20%
No
180 seconds
180 seconds
Auto
Analog Sensor
55°F
Capability Installation Instructions
37
1
Available Values
0 to 4,914,302
* BACnet/MSTP communication mode
4 to 127
* BACnet/MSTP communication mode
ISO 10646 (UCS-2), ANSI X3.4
(US-ASCII)
0 to 127
2-Pipe, 4-Pipe, VAV
0 to 10 VDC
0 to 10 VDC
0 to 10 minutes
Single Speed, Multi-speed, Variable
Speed
* Fan coil units only
0 to 10 VDC
* Fan coil units only, variable speed fan
0 to 10 VDC, proportional
* Fan coil units only, variable speed fan
0 to 100%
* Fan coil units only, variable speed fan
0 to 100%
* Fan coil units only, multi-speed fan
0 to 100%
* Fan coil units only, multi-speed fan
Yes (True) or No (False)
0 to 100%
* VAV units with reheat installed
Yes or No
* Fan coil units with reheat installed
0 to 360 second
* Reheat installed
0 to 360 seconds
* Reheat installed
Auto, Cooling, or Heating
* Non 4-Pipe units
Analog Sensor, Heating NC, Cooling NC
* Changeover Mode = Auto
40 to 200°F (4 to 93°C)
* Supply temp type = analog sensor